40
8 Operating
MANUAL CEAG AUtoMAtiC tEst systEM At-s
+
40071860177 (C) December 2016 www.ceag.de
Starting point:
Main screen
<Menu>
Selecting the main menu:
/
: Select Basic settings in the main
menu
1
)
2
)
<Menu> key: back to main screen (cancel)
<ok>
key: confirm selection, show selec-
ted menu (with the Function test
selection)
3
)
1
) visible area of the main menu
(with screen roll (scroll-)function)
2
) currently non-visible area
3
) highlighting of a selection
Menu
selection
Lanuage
Date & time
Function test
Delay on mains return
Test & status menu
Block,reset
Basic settings
DLS/TLS setup
Circuit setup
Luminaire setup
Memory card
1
4
3
6
7
2
5
8.4 Operating the CU S
+
control module
LEDs (1) in the top row indicate running functions that were
initiated with the Function buttons (2) aside.
The 3 left-hand buttons initiate present functions of the
controller software for the CU S+ control module:
– <Test> activates a simulated mains failure for testing
the emergency lighting equipments while the button
is pressed. A short button press simulates a 5 second
mains failure.
– <FT> activates the menu option F-Test start / cancel
The controller software performs a function test whose
progress and results are output on the display (5). An
F-Test tests the final circuits and the luminaires connected
to them. You will find further information about this in the
description of the related program function in the following
section.
– <DT> without function
Further details about the system´s operating status and
faults can be requested in the Test- & Status menu.
The Main Menu of the controller software is opened from
the main screen with the key (7), refered to in the the
current test as <menu>. This key is also used to return to
the previous menu level until the main screen appears on
the graphic display (5).
Graphic display
(main screen during normal
operation)
The control module can be programmed to assign func-
tions to the 3 right-hand function buttons F1 ... F3; e. g.
the first button F 1 can be assigned the function manual
reset.
The other LEDs (3) indicate:
– Ready for operation
– Feed from the power source for safety services (emer-
gency operation),
– Failures that can be further analysed using the control
module´s menu options.
The control keys on the keypad (6) are used to initiate the
program functions on the controller software or change
their parameter settings.