15 Appendix
15.2 Modbus/TCP Register Map
62
BreakerVisu
06/16 MN01210001Z-EN
www.eaton.com
Table 48:
SmartWire-DT device parameters
n = (x * 150)
+ 4800,
x = Smart-
Wire-DT
number
Device
Notes
n + 0
Parameter 1-16 present
-
1 stands for a present parameter at a
specific place. Dec 11 = 1012 (bin) = Param-
eters 1, 2, and 4 present.
n + 1
Parameter 17-32 present
-
n + 2
Parameter 33-48 present
-
n + 3
Circuit-breaker position
-
1 = Open, 2 = Closed, 3 = Tripped.
n + 4
Calculated circuit-breaker status
-
n + 5
ir* Rated operational current
A
n + 6
If there is circuit-breaker wear
BOOL
n + 7
Mechanical circuit-breaker wear
%
n + 8
Electrical circuit-breaker wear
%
n + 9
reserved
-
n + 10
Status SmartWire-DT
n + 11
Status 0
n + 12
Status 1
n + 13
Status 2
n + 14
Temperature simulation max.
%
n + 15
Current I1
The data has the same format as the data
read from the device. This makes trans-
parent data processing possible.
n + 16
Current I2
n + 17
Current I3
n + 18
Current IN
n + 19
Voltage L1-N/L1-L2
n + 20
Voltage L2 - N/L2- L3
n + 21
Voltage L3- N/L3 - L1
n + 22
Ø Power factor
n + 23
Active power L1
n + 24
n + 25
Active power L2
n + 26
n + 27
Active power L3
n + 28
n + 29
Reactive power L1
n + 30
n + 31
Reactive power L2
n + 32