background image

IB140012EN

For more information visit: www.eaton.com

Instructional Booklet

Effective: March 2021

Page

 

3

Operation and Maintenance Manual,
Automatic Transfer Switch Controller, ATC-900

1.2 Background

Transfer switches are used to protect critical electrical loads 

against loss of power. The load’s normal power source is backed 

up by a secondary (emergency) power source. A transfer switch is 

connected to both the normal and emergency sources and sup-

plies the load with power from one of these two sources. In the 

event that power is lost from the normal source, the transfer 

switch transfers the load to the secondary source. Transfer can be 

automatic or manual depending upon the type of transfer switch 

equipment being used. Once normal power is restored, the load is 

transferred back to the normal power source. The transfer switch, 

in this manual, could be a Power Frame Switch/Breaker, Molded 

Case Switch/Breaker, or a Contactor type.
In automatic transfer switch equipment, the switch’s intelligence 

system initiates the transfer when normal power fails or falls out-

side a preset threshold. If the emergency source is a standby gen-

erator, the transfer switch initiates generator starting and 

transfers to the emergency source when sufficient generator volt-

age is available. When normal power is restored, the transfer 

switch automatically transfers back and initiates generator engine 

shutdown.
An automatic transfer switch consists of three basic elements:

1. Main contacts to connect and disconnect the load to and from 

the source of power

2. A transfer mechanism to affect the transfer of the main con-

tacts from source to source

3. Intelligence/supervisory circuits to constantly monitor the con-

dition of the power sources and thus provide the intelligence 

necessary for the switch and related circuit operation

This document deals with the third basic element of the automatic 

transfer switch, the required intelligence/ supervisory circuits. 

Prior to the introduction of ATC-900, this function was performed 

by a door mounted logic panel. The logic panel could be the relay 

logic type or the solid state logic type. In either case, the panel 

consists of a number of individually mounted and wired devices 

offering a limited amount of system flexibility, especially in the 

case of the relay logic design. The ATC-900 brings intelligence, 

supervisory and programming capabilities, never before available, 

to automatic transfer switch equipment.

1.3 Product Overview

The ATC-900 is a comprehensive, multi-function, microprocessor- 

based automatic transfer switch controller. It is a compact, self-

contained, panel mounted device designed to replace traditional 

relay and solid state logic panels (Figures 

2

and

3

).

Designed to meet the needs of markets worldwide, the ATC-900 

meets the following standards:

ULT 991 Effects of shipping and storage test

Thermal cycling test

Humidity test

UL 1008 Dielectric test

FCC Part 15 Conducted/radiated emissions (Class B)

CISPR 11 Conducted/radiated emissions (Class A)

IEC 61000-4-2 Electrostatic discharge test

IEC 61000-4-3 Radiated susceptibility tests

IEC 61000-4-4 Fast transient tests

IEC 61000-4-5 Surge withstand tests

IEC 61000-4-6 Conducted immunity tests

IEC 61000-4-11 Voltage dips and interruptions

IEC 61000-3-2 Harmonics

IEC 61000-3-3 Voltage flicker/fluctuation

Seismic IBC/CBC certified

CSA conformance C22.2 No. 178-1978 (reaffirmed 1992)

The ATC-900 provides an unmatched degree of programmed flexi-

bility to address the needs of any system. It operates from most 

system voltages available worldwide at 50 or 60 Hertz (and 24 

VDC using the CT Module option). In addition, a period of no con-

trol power operation is provided. The ATC-900 monitors the condi-

tion of the 3-phase line-to-line voltage and frequency of both the 

Normal and Emergency sources. It can also be programmed for sin-

gle-phase operation. The ATC-900 provides the necessary intelli-

gence to insure that the switch operates properly through a series 

of programmed sensing and timing functions.
The ATC-900 will form fit into the opening of the ATC-600/800 

and an easy upgrade kit is available for previous switch wiring.

A standard ATC-900 will:

Monitor Normal and Emergency source voltages and frequen-

cies

Provide second to none Event Summary, Hi-Speed Capture, and 

History information

Permit customer programming including I/O

Display real time and historical information through a color 4.5 

inch TFT display

System diagnostics through the display

All I/O are available to the user

Features are opened to user

Provides serial communications (Modbus RTU) and a USB port. 

Ethernet communication optional. 

Provide faceplate source/load status indications (MIMIC bus)

1.4 Functions/Features/Options

The primary function of ATC-900 is to accurately monitor power 

sources and provide the necessary intelligence to operate a trans-

fer switch in an appropriate and timely manner. In addition, 

ATC-900 provides useful present and historical data, reliable two-

way communications, and programming through the device’s face-

plate or communications. ATC-900 features digital signal proces-

sor (DSP) technology to provide and maintain superior precision 

and versatility during both programming and data access.

1.4.1 Operational Simplicity

From installation, to programming, to usage, the ATC-900 was 

designed with operational simplicity in mind. Only one style needs 

to be considered, regardless of input/output requirements or sys-

tem voltages and frequencies. ATC-900 provides the functionality 

of numerous other devices combined in one package that mounts 

in less than 7 by 11 inches of panel space.
The user friendly front panel interface simplifies routine operation, 

programming, data presentation and setting adjustments. A large 

color display provides flexibility and ease of use. The operation of 

front panel membrane pushbuttons moves the ATC-900 display 

from function to function or step to step within menus. A single 

LED at the top of the faceplate provide an immediate indication as 

to the device’s operational mode. An integrated Help Mode provides 

immediate user assistance in the form of English language message 

displays through the use of a front panel Help pushbutton.
The ATC-900 is communications ready, including Modbus 485, 

Ethernet (External), and USB for thumb drives (memory sticks).

Summary of Contents for ATC-900

Page 1: ...escription Page 1 Introduction 2 2 Hardware Description 6 3 Operator Panel and Display Menus 12 4 Operation 15 5 Setpoint Programming and I O Programming Using the Color Display 18 6 Troubleshooting a...

Page 2: ...e strict liability or otherwise for any special indirect incidental or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system co...

Page 3: ...00 4 3 Radiated susceptibility tests IEC 61000 4 4 Fast transient tests IEC 61000 4 5 Surge withstand tests IEC 61000 4 6 Conducted immunity tests IEC 61000 4 11 Voltage dips and interruptions IEC 610...

Page 4: ...ble I Os are covered in Section 5 The only item that is optional for the transfer switch is the closed transition optional feature The closed transition operation is cov ered in section 1 5 3 The swi...

Page 5: ...ust be synchronized in frequency phase and voltage before the transfer is initiated In phase transition is a feature that will allow a transfer between two live sources only when the phase difference...

Page 6: ...liarize the reader with ATC 900 hardware its nomenclature and to list the unit s specifica tions The information presented is divided into the following four parts Operator Panel Rear Access Area Exte...

Page 7: ...er stand LED type 4 Color Display Window easy to read monitored param eters setpoints and messages 5 Bypass Timer used simultaneously to bypass timers such as TDNE TDEN and TDEC 6 Help Pushbutton prov...

Page 8: ...n the controller The DCT is used to measure load current when selective load shed is enabled The DCT Module also has a 24 Vdc input for powering the ATC 900 controller If 120 VAC and 24 Vdc is supplie...

Page 9: ...T 991 Effects of shipping and storage test Thermal cycling test Humidity test UL 1008 Dielectric test FCC Part 15 Conducted radiated emissions Class A CISPR 11 Conducted radiated emissions Class A IEC...

Page 10: ...igure 5 I O Module s Wiring 2 5 3 Ethernet Module Description The Ethernet Communications Module is an optional accessory that operates as a communicating device in conjunction with a the ATC 900 via...

Page 11: ...idity non condensing Enclosure Compatibility NEMA 12 standard mounting NEMA 4 4X mounted with gasket between panel and device faceplate NEMA 3R outdoor UV Resistant ATC 900 Faceplate System Voltage Ap...

Page 12: ...s like the up down left and right Arrows will also continue to scroll if they are pressed and not released 3 3 2 Help Pushbutton When the Help pushbutton is pressed and released with the ATC 900 in an...

Page 13: ...e Diff iv In Phase Transition No Sync to Alarm or Open v Frequency Diff vi Sync Timer vii Time Delay Neutral TDN viii Load Decay d Screen 4 Setpoints Switch Type Settings 4 of 4 2 View Setpoints Time...

Page 14: ...Event Details c Hi Speed Captures d Event Data 8 System Info Figure 7b a Style b Transitions c GO Number d Serial Number e Fixed I O f Firmware Versions g Time Date 9 USB Menu a Save Setpoints b Load...

Page 15: ...ure 2 for a graphical representation and position of all input connections There are two types of I Os programmable and fixed Most I O are programmable by the user at any time There are a few that are...

Page 16: ...t input is de activated Bypass Timers Input This momentary contact will bypass the timer for TDEN TDNE TDN TDES and TDEC By pushing the Help and Enter buttons on the front of the controller Bypass Tim...

Page 17: ...lay Neutral TDN Time Delay Normal Disconnect TDND Time Delay Normal Reconnect TDNR Time Delay Emergency Disconnect TDED Time Delay Emergency Reconnect TDER Pre transfer Delay Signal TD PRE TRAN Post t...

Page 18: ...the communications port Users can reprogram setpoints as well as other parameters Up to four optional I O modules each having four in and four out programmable I Os can be used with the ATC 900 That...

Page 19: ...ements of the Load Note that the DCT module is required to display Load current Watts VAR VA and power factor Other wise only voltage measurements will be shown See Section 2 for the DCT Module specif...

Page 20: ...mmable I O The System Setpoints screen contains normal voltage frequency preferred source CT Ratio communications closed or open and several more After the initial setting of these system setpoints th...

Page 21: ...tenance Manual Automatic Transfer Switch Controller ATC 900 Figure 11 Setting Setpoints All setpoints are set in this way The display gives the user a quick look at not just one setpoint but the whole...

Page 22: ...engine 2 start 259 Minutes 0 03 4A Time delay engine cool off 0 9999 seconds 5 00 7A Time delay engine fail timer 0 60 seconds 0 06 Unbalance phase loss time delay 0 30 seconds 0 20 Any TDES value abo...

Page 23: ...Selective Load Shed General Alarm Indication Contact Monitor Mode ATS in Test Engine Test Aborted Cooldown in Process Engine Start Contact Status Gen 1 2 LOAD SHED Emergency Inhibit On ATS on Bypass L...

Page 24: ...ample When the I O is Fixed the display will show the particular I O in the designated slot The display will show a fixed I O as black instead of blue Table 8 shows the features and the I O of the con...

Page 25: ...ne Test 6B Engine Test Pushbutton on Panel S S S S S S S S S 6C Remote Engine Test INPUT P P P P P P P P P I 7B Time Delay Engine Fail TDEF Adjustable 0 60 Sec S S S S S S S S S Pushbutton Bypass 8E B...

Page 26: ...Transfer Signal Contacts Form C P P P P P P P P P O 36 Load Shed S2 Inhibit INPUT P P P P P P P P P I 36A Load Shed S2 Inhibit w Keyed Switch INPUT OF OF OF OF OF OF OF OF OF I 37 Go to Isolated Posit...

Page 27: ...81F Engine Start Contact Status Gen 1 Gen 2 OUTPUT P P P P P P P P P O 81G LOAD SHED S2 Inhibit On OUTPUT P P P P P P P P P O 81GL LOAD SHED S2 Inhibit On w white indicating light OF OF OF OF OF OF O...

Page 28: ...Stuck waiting for Neutral position ATC 900 is malfunctioning Verify that control power is connected at J7 and that it is within specifications Mechanical problem No inputfrom limit switch Replace the...

Page 29: ...not locked in Statis lamp is on Monitor Mode Unit is in manual mode Close the door s assure contactor s is locked in turn top user switch to auto matic Unit displays Lockout No contact closure at Loc...

Page 30: ...ine voltage and frequency available at ter minals N1 N2 and N3 Record the readings If YES Proceed to Step 4 If NO Check Preferred source Step 4 Is the transformer voltage selector plug in the correct...

Page 31: ...o be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to ensure reconnection can be correctly performed Taking a pi...

Page 32: ...removed to when the switch transferred includ ing engine start and source available Historical Data Figure 15 Historical Data Screen The Historical Data display indicates historical and cumulative co...

Page 33: ...splay Insufficient Memory To load controller setpoints from a setpoint file on your USB flash drive use the arrow keys to navigate to the Load Setpoints icon and press Enter The Load Setpoints feature...

Page 34: ...defined period of time TDER with a range of 0 60 seconds A flowchart example is shown in Appendix C Feature System Nominal Frequency NOMF There are only two choices for system nominal frequency of the...

Page 35: ...pushbutton remote switch to any of the Inputs to do the same function This feature is usually used in testing when it is not desirable to wait for completion of the tim ing sequence Feature 9B Mainten...

Page 36: ...bal ance must drop to a value that is below the pickup setting to stop the timer or to become available after the timer expires This can be disabled in the setpoint settings under menu 3 in the Setpoi...

Page 37: ...Source See the Con trol Inputs section for more information The ATC 900 when used in conjunction with the optional DCT metering module has the ability to shed and pick up loads based on available gene...

Page 38: ...er failure of S2 The Generator Fail Alarm remains active until either manually cleared or until Second ary In is removed and re asserted to start a new session Once a generator fails the other generat...

Page 39: ...Source Gen Start Set Emergency Source to Idle state Yes No No Set transfer switch to Emergency Source No TDN or TDNE if switch was previously on Normal Source No Change to Preferred Source Gen Start o...

Page 40: ...C Set Source 2 to Idle state Yes No No Set transfer switch to Source 2 No TDN or TDNE if switch was previously on Source 1 Turn off Source 1 Gen Start after fixed 5 minute TDEC Set Source 1 to Idle st...

Page 41: ...se of Phase Angle 13 Source 1 Mech Failed to Open The Source 1 Mechanism for a breaker or contactor did not open 14 Source 1 Mech Failed to Close The Source 1 Mechanism for a breaker or contactor did...

Page 42: ...1 is not available to switch to neutral 3 Time Delay Normal to Emergency Countdown timer before normal is opened for transfer to emergency source 4 Time Delay Normal Reconnect Countdown timer for whe...

Page 43: ...e manual retransfer feature Selection of this option automatically adds option 29J 36 I Load Shed Emergency Inhibit Enables load shed S2 Inhibit See 36A 36A I Load Shed Emergency Inhibit w Keyed Switc...

Page 44: ...rovides remote indication that the ATS is currently running a test The test could be initiated by the device panel engine test pushbutton or automatically using the programmed engine excersier 81D O E...

Page 45: ...UW WR FRXQWGRZQ DIWHU WKH 6RXUFH PDLQ FRQWDFWV FORVH 7 1 WLPH GHOD H SLUHV 25 9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW ORVH 6RXUFH PDLQ FRQWDFWV DFWXDWH UHOD 6RXUFH LV SRZHULQJ...

Page 46: ...HV ZKHQ SRVW WUDQVIHU FRQILJXUHG 7 WLPH GHOD H SLUHV 5HPRYH QJLQH 6WDUW VLJQDO GH DFWXDWH JHQ VWDUW UHOD 6HQG QJLQH 6WDUW VLJQDO DFWXDWH JHQ VWDUW UHOD 1R HV HV 1R 6 QF WLPH GHOD VWDUWV FRXQWGRZQ DYH...

Page 47: ...9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW HV 1R 3RVW WUDQVIHU WLPH GHOD H SLUHV ZKHQ SRVW WUDQVIHU FRQILJXUHG V IDOOEDFN WR RSHQ LQ SKDVH WUDQVLWLRQ FRQILJXUHG 6 QF WLPH GHOD VW...

Page 48: ...Normal TDND 0 Disconnected from both TDNR Counting Down Normal Available Set TDNR Emergency Available Set TDNE Emergency Unavailable Clear TDNE Normal Available Clear TDND Normal Unavailable Set TDND...

Page 49: ...ailable fail safe transfer TDED Time Delay Emergency Disconnect 0 10 sec TDEN Time Delay Emergency to Normal 0 9999 sec TDER Time delay Emergency Reconnect 0 60 sec Disconnected from both No Timers Co...

Page 50: ...ADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability...

Reviews: