4.3 Switch Type Setpoints

There is a feature that the user can set the SWITCH TYPE 

(Device) by simply changing the setpoint. See Tables 4 and 5 

below .This allows the ATC-900 controller to be completely pro-

grammable by the end user with all options available. It cannot be 

read/changed by MODBUS. The feature types are the following 

and depends on if the switch is an open type or a closed (and 

open) type. See section 5.2 on how to set the switch type.

Table 4. For Open Transition Controllers

Table 5. For Closed Transition Controllers

4.4 Test Mode

The Engine Test is intended to allow periodic system tests. The 

exact test conditions are determined by the programmed set-

points. The operator-selected parameters include setting the 

engine run time and the Test Mode. Refer to Table 7 for test pro-

gramming details.

There are four test modes:
1 No Load Engine Run Test;
2 Load Transfer Engine Test; or
3 External: Select No Load or Load Transfer based on Engine Test 

Mode Select programmable input.

4 Disabled.

IF THE ATS IS UNABLE TO PROCESS A ENGINE TEST REQUEST 

DUE TO THE ATS STATUS, THE REQUEST IS IGNORED.

When the Engine Test pushbutton is pressed, the display will 

prompt the user to input a password (factory set to 0900).  Use 

the arrow keys to enter the password, then press the right arrow 

key to highlight the "Enter Password" icon and press the Enter 

key.

The ATC-900 will display the Time Delay on Engine Starting 

(TDES) timer countdown. Once the TDES countdown reaches 

zero, the ATC-900 Controller will initiate an engine start. The 

engine run duration will be per the Engine Run Test Time setpoint.

If Test Mode is set to "Engine Run", then the switch will start the 

non-preferred generator, but will not initiate a transfer to the non-

preferred source. 

If Test Mode is set to "Load Transfer", then the switch will start 

the non-preferred generator and initiate a transfer to the non-pre-

ferred source once the generator output has reached the specified 

setpoints.

All enabled and programmed time delays will be performed per the 

setpoints during an engine test. The time delays will appear on the 

LCD Display with “countdown to zero” when active. Depending 

on the setpoints and the optional features selected with the ATC-

900 Controller, these can include:

Time Delay Engine Start (TDES);

Time Delay Normal to Emergency (TDNE);

Time Delay Emergency to Normal (TDEN);

Time Delay for Engine Cooldown (TDEC);

Time Delay Neutral (TDN);

Time Delay Normal Disconnect (TDND)*

Time Delay Normal Reconnect (TDNR)*

Time Delay Emergency Disconnect (TDED)*

Time Delay Emergency Reconnect (TDER)*

Pre-transfer Delay Signal (TD PRE-TRAN).

Post-transfer Delay Signal (TD POST-TRAN).

* See flowchart example in Appendix C.

All operations are “Failsafe”, meaning they prevent disconnection 

from the only available power source and also force a transfer or 

re-transfer operation to the only available power source. 

During an engine test, if the Engine Test pushbutton is pressed a 

second time before the Engine Test is complete, the Engine Test 

will be terminated. An engine test may also be aborted in the fol-

lowing ways:

1. If the Emergency Source does not become available within 90 

seconds of the ATC-900 providing the engine start command;

2. If, during the TDNE countdown, the Emergency Source goes 

unavailable more than three times (Each time, TDNE will 

restart);

3. If the Emergency Source is powering the load and it goes 

unavailable for more than the TDEF (Time Delay Engine Fail-

ure) setting; and

4. If the Normal source becomes unavailable.

When an engine test is aborted due to an unavailable source 

during TDNE countdown, the Alarm relay will energize, a “TEST 

ABORTED” message will appear on the display, and the event will 

be logged into the Transfer History as “Aborted Test” Aborted.

4.5 USB Interface (Event Status-Setpoints)

Every ATC-900 transfer switch includes a front panel, NEMA 4X 

rated USB port for use in configuring set points or downloading 

event data to a USB flash drive. The USB interface is brought to 

the front of the enclosure to enable flash memory (memory stick) 

to be plugged in to upload or download data such as History Data 

Logging, or Setpoints. The USB interface will only work with 

memory devices and not laptop computers. 

4.5.1 Upload/Download Setpoints via USB

To reduce the time spent on site for commissioning, set points 

can be configured at a PC using the ATC-900 configuration 

software and saved to a USB flash drive to be uploaded to one or 

multiple controllers. Set points are also easily copied from one 

controller to another. See EASE, section 7.1, last paragraph.

SWITCH TYPE

TRANSITIONS

Unprogrammed

Open Style

2-Position Contactor

In-Phase/Open

Breakers with Motor Operator

Open/Delayed

Power Breakers

In-Phase/Open/Delayed

3-Position Contactor

In-Phase/Open/Delayed

Medium Voltage Switch

In-Phase/Open/Delayed

Medium Voltage Breaker

In-Phase/Open/Delayed

3000 Amp Contactor

In-Phase/Open/Delayed

SWITCH TYPE

TRANSITIONS

Unprogrammed

Closed Style

Power Breakers

Closed/In-Phase/Open/Delayed

3-Position Contactor

Closed/In-Phase/Open/Delayed

Medium Voltage Switch

Closed/In-Phase/Open/Delayed

Medium Voltage Breaker

Closed/In-Phase/Open/Delayed

3000 Amp Contactor

Closed/In-Phase/Open/Delayed

Summary of Contents for ATC-900

Page 1: ...escription Page 1 Introduction 2 2 Hardware Description 6 3 Operator Panel and Display Menus 12 4 Operation 15 5 Setpoint Programming and I O Programming Using the Color Display 18 6 Troubleshooting a...

Page 2: ...e strict liability or otherwise for any special indirect incidental or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system co...

Page 3: ...00 4 3 Radiated susceptibility tests IEC 61000 4 4 Fast transient tests IEC 61000 4 5 Surge withstand tests IEC 61000 4 6 Conducted immunity tests IEC 61000 4 11 Voltage dips and interruptions IEC 610...

Page 4: ...ble I Os are covered in Section 5 The only item that is optional for the transfer switch is the closed transition optional feature The closed transition operation is cov ered in section 1 5 3 The swi...

Page 5: ...ust be synchronized in frequency phase and voltage before the transfer is initiated In phase transition is a feature that will allow a transfer between two live sources only when the phase difference...

Page 6: ...liarize the reader with ATC 900 hardware its nomenclature and to list the unit s specifica tions The information presented is divided into the following four parts Operator Panel Rear Access Area Exte...

Page 7: ...er stand LED type 4 Color Display Window easy to read monitored param eters setpoints and messages 5 Bypass Timer used simultaneously to bypass timers such as TDNE TDEN and TDEC 6 Help Pushbutton prov...

Page 8: ...n the controller The DCT is used to measure load current when selective load shed is enabled The DCT Module also has a 24 Vdc input for powering the ATC 900 controller If 120 VAC and 24 Vdc is supplie...

Page 9: ...T 991 Effects of shipping and storage test Thermal cycling test Humidity test UL 1008 Dielectric test FCC Part 15 Conducted radiated emissions Class A CISPR 11 Conducted radiated emissions Class A IEC...

Page 10: ...igure 5 I O Module s Wiring 2 5 3 Ethernet Module Description The Ethernet Communications Module is an optional accessory that operates as a communicating device in conjunction with a the ATC 900 via...

Page 11: ...idity non condensing Enclosure Compatibility NEMA 12 standard mounting NEMA 4 4X mounted with gasket between panel and device faceplate NEMA 3R outdoor UV Resistant ATC 900 Faceplate System Voltage Ap...

Page 12: ...s like the up down left and right Arrows will also continue to scroll if they are pressed and not released 3 3 2 Help Pushbutton When the Help pushbutton is pressed and released with the ATC 900 in an...

Page 13: ...e Diff iv In Phase Transition No Sync to Alarm or Open v Frequency Diff vi Sync Timer vii Time Delay Neutral TDN viii Load Decay d Screen 4 Setpoints Switch Type Settings 4 of 4 2 View Setpoints Time...

Page 14: ...Event Details c Hi Speed Captures d Event Data 8 System Info Figure 7b a Style b Transitions c GO Number d Serial Number e Fixed I O f Firmware Versions g Time Date 9 USB Menu a Save Setpoints b Load...

Page 15: ...ure 2 for a graphical representation and position of all input connections There are two types of I Os programmable and fixed Most I O are programmable by the user at any time There are a few that are...

Page 16: ...t input is de activated Bypass Timers Input This momentary contact will bypass the timer for TDEN TDNE TDN TDES and TDEC By pushing the Help and Enter buttons on the front of the controller Bypass Tim...

Page 17: ...lay Neutral TDN Time Delay Normal Disconnect TDND Time Delay Normal Reconnect TDNR Time Delay Emergency Disconnect TDED Time Delay Emergency Reconnect TDER Pre transfer Delay Signal TD PRE TRAN Post t...

Page 18: ...the communications port Users can reprogram setpoints as well as other parameters Up to four optional I O modules each having four in and four out programmable I Os can be used with the ATC 900 That...

Page 19: ...ements of the Load Note that the DCT module is required to display Load current Watts VAR VA and power factor Other wise only voltage measurements will be shown See Section 2 for the DCT Module specif...

Page 20: ...mmable I O The System Setpoints screen contains normal voltage frequency preferred source CT Ratio communications closed or open and several more After the initial setting of these system setpoints th...

Page 21: ...tenance Manual Automatic Transfer Switch Controller ATC 900 Figure 11 Setting Setpoints All setpoints are set in this way The display gives the user a quick look at not just one setpoint but the whole...

Page 22: ...engine 2 start 259 Minutes 0 03 4A Time delay engine cool off 0 9999 seconds 5 00 7A Time delay engine fail timer 0 60 seconds 0 06 Unbalance phase loss time delay 0 30 seconds 0 20 Any TDES value abo...

Page 23: ...Selective Load Shed General Alarm Indication Contact Monitor Mode ATS in Test Engine Test Aborted Cooldown in Process Engine Start Contact Status Gen 1 2 LOAD SHED Emergency Inhibit On ATS on Bypass L...

Page 24: ...ample When the I O is Fixed the display will show the particular I O in the designated slot The display will show a fixed I O as black instead of blue Table 8 shows the features and the I O of the con...

Page 25: ...ne Test 6B Engine Test Pushbutton on Panel S S S S S S S S S 6C Remote Engine Test INPUT P P P P P P P P P I 7B Time Delay Engine Fail TDEF Adjustable 0 60 Sec S S S S S S S S S Pushbutton Bypass 8E B...

Page 26: ...Transfer Signal Contacts Form C P P P P P P P P P O 36 Load Shed S2 Inhibit INPUT P P P P P P P P P I 36A Load Shed S2 Inhibit w Keyed Switch INPUT OF OF OF OF OF OF OF OF OF I 37 Go to Isolated Posit...

Page 27: ...81F Engine Start Contact Status Gen 1 Gen 2 OUTPUT P P P P P P P P P O 81G LOAD SHED S2 Inhibit On OUTPUT P P P P P P P P P O 81GL LOAD SHED S2 Inhibit On w white indicating light OF OF OF OF OF OF O...

Page 28: ...Stuck waiting for Neutral position ATC 900 is malfunctioning Verify that control power is connected at J7 and that it is within specifications Mechanical problem No inputfrom limit switch Replace the...

Page 29: ...not locked in Statis lamp is on Monitor Mode Unit is in manual mode Close the door s assure contactor s is locked in turn top user switch to auto matic Unit displays Lockout No contact closure at Loc...

Page 30: ...ine voltage and frequency available at ter minals N1 N2 and N3 Record the readings If YES Proceed to Step 4 If NO Check Preferred source Step 4 Is the transformer voltage selector plug in the correct...

Page 31: ...o be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to ensure reconnection can be correctly performed Taking a pi...

Page 32: ...removed to when the switch transferred includ ing engine start and source available Historical Data Figure 15 Historical Data Screen The Historical Data display indicates historical and cumulative co...

Page 33: ...splay Insufficient Memory To load controller setpoints from a setpoint file on your USB flash drive use the arrow keys to navigate to the Load Setpoints icon and press Enter The Load Setpoints feature...

Page 34: ...defined period of time TDER with a range of 0 60 seconds A flowchart example is shown in Appendix C Feature System Nominal Frequency NOMF There are only two choices for system nominal frequency of the...

Page 35: ...pushbutton remote switch to any of the Inputs to do the same function This feature is usually used in testing when it is not desirable to wait for completion of the tim ing sequence Feature 9B Mainten...

Page 36: ...bal ance must drop to a value that is below the pickup setting to stop the timer or to become available after the timer expires This can be disabled in the setpoint settings under menu 3 in the Setpoi...

Page 37: ...Source See the Con trol Inputs section for more information The ATC 900 when used in conjunction with the optional DCT metering module has the ability to shed and pick up loads based on available gene...

Page 38: ...er failure of S2 The Generator Fail Alarm remains active until either manually cleared or until Second ary In is removed and re asserted to start a new session Once a generator fails the other generat...

Page 39: ...Source Gen Start Set Emergency Source to Idle state Yes No No Set transfer switch to Emergency Source No TDN or TDNE if switch was previously on Normal Source No Change to Preferred Source Gen Start o...

Page 40: ...C Set Source 2 to Idle state Yes No No Set transfer switch to Source 2 No TDN or TDNE if switch was previously on Source 1 Turn off Source 1 Gen Start after fixed 5 minute TDEC Set Source 1 to Idle st...

Page 41: ...se of Phase Angle 13 Source 1 Mech Failed to Open The Source 1 Mechanism for a breaker or contactor did not open 14 Source 1 Mech Failed to Close The Source 1 Mechanism for a breaker or contactor did...

Page 42: ...1 is not available to switch to neutral 3 Time Delay Normal to Emergency Countdown timer before normal is opened for transfer to emergency source 4 Time Delay Normal Reconnect Countdown timer for whe...

Page 43: ...e manual retransfer feature Selection of this option automatically adds option 29J 36 I Load Shed Emergency Inhibit Enables load shed S2 Inhibit See 36A 36A I Load Shed Emergency Inhibit w Keyed Switc...

Page 44: ...rovides remote indication that the ATS is currently running a test The test could be initiated by the device panel engine test pushbutton or automatically using the programmed engine excersier 81D O E...

Page 45: ...UW WR FRXQWGRZQ DIWHU WKH 6RXUFH PDLQ FRQWDFWV FORVH 7 1 WLPH GHOD H SLUHV 25 9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW ORVH 6RXUFH PDLQ FRQWDFWV DFWXDWH UHOD 6RXUFH LV SRZHULQJ...

Page 46: ...HV ZKHQ SRVW WUDQVIHU FRQILJXUHG 7 WLPH GHOD H SLUHV 5HPRYH QJLQH 6WDUW VLJQDO GH DFWXDWH JHQ VWDUW UHOD 6HQG QJLQH 6WDUW VLJQDO DFWXDWH JHQ VWDUW UHOD 1R HV HV 1R 6 QF WLPH GHOD VWDUWV FRXQWGRZQ DYH...

Page 47: ...9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW HV 1R 3RVW WUDQVIHU WLPH GHOD H SLUHV ZKHQ SRVW WUDQVIHU FRQILJXUHG V IDOOEDFN WR RSHQ LQ SKDVH WUDQVLWLRQ FRQILJXUHG 6 QF WLPH GHOD VW...

Page 48: ...Normal TDND 0 Disconnected from both TDNR Counting Down Normal Available Set TDNR Emergency Available Set TDNE Emergency Unavailable Clear TDNE Normal Available Clear TDND Normal Unavailable Set TDND...

Page 49: ...ailable fail safe transfer TDED Time Delay Emergency Disconnect 0 10 sec TDEN Time Delay Emergency to Normal 0 9999 sec TDER Time delay Emergency Reconnect 0 60 sec Disconnected from both No Timers Co...

Page 50: ...ADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability...

Reviews: