Operation and Maintenance Manual,
Automatic Transfer Switch Controller, ATC-900

Appendix B: I/O Descriptions

TYPE

I/O

I/O DEFINITIONS

SUMMARY

6C

I

Remote Engine Test 

Provides an input to initiate a test to simulate a loss of the Source 1 as standard.  All programmed time delays (TDNE, TDEN, etc.) will be per-

formed as part of the test.  Engine run ime of the test is equal to the plant exerciser programmed set point. All tests are fail-safe protected. 

The test is initiated via remote momentary contact closure.

8E

I

Bypass Timers 

The Time Delay Bypass Pushbutton contact, when closed, will reduce any or all of the programmed time delay to zero. Must be executed when 

the appropriate timer is displayed on the controller. The bypass time delay feature is initiated via remote momentary contact closure. (The 

front of the controller has a Bypass Timer also).

8F

I

Bypass Timers w external 

push button

 Provides a means to bypass the time delays with via a device panel mounted push-button switch.

10A

I

Preferred Source Selector 

Provides a means to designate either Source 1 or Source 2 as the “Preferred” Source using a remote contact or device panel mounted contact 

closure.  The “Preferred” Source is the source that the transfer switch will connect the load to if it is available. The Preferred Source setpoint 

must be set to "External" to use this feature.

10C

I

Preferred Source Selector w/

selector switch

Provides a means to designate either Source 1 or Source 2 as the “Preferred” Source via device panel mounted selector switch control.  The 

“Preferred” Source is the source that the transfer switch will connect the load to if it is available. The Preferred Source setpoint must be set 

to "External" to use this feature.

23N

 I 

 Engine Test Mode Select

Input to enable load or no load test

26D

I

Go to Emergency (S2)

Provides a means to send the switch to the Non-preferred (Emergency) sourceproviding the voltage and frequency are within the limits of the 

setpoints.  This signal will initiate an engine start.

26E

I

Go to Emergency (S2) Input 

w/selector Switch

Provides a device panel mounted selector switch labeled, "Auto/Go to Source 2", to initiate a transfer to the Source 2 power source. This 

includes starting the generator, performing the programmed time delays and the transfer operation.  Re-transfer will occur when the external 

contact is opened. This is a fail-safe function.

29E

I

ATS in Bypass 

A signal to the controller to specify that the switch is in the bypass position

29G

I

Selector Switch for Auto & 

Non-Auto 

Provides a device panel mounted selector switch to specify if the switch is in the automaitc or normal mode or if the switch is in Non-auto-

matic electrical mode.

29K

I

Enable Manual Retrtansfer

Provides an input to remotely initiate a manual retransfer from the Non-preferred source to the Preferred source.

29J

I

Enable Manual Pushbutton 

Transfer E to N or N to E

Provides an input to remotely initiate a manual retransfer from the Non-preferred source to the Preferred source or vice-versa.

29L

I

Manual Retransfer On/Off 

Provides an input to remotely enable or disable the manual retransfer feature.

29M

I

Manual Retransfer On/Off 

Input w/selector switch

Provides an device panel mounted selector switch to enable or disable the manual retransfer feature.  Selection of this option automatically 

adds option 29J.

36

I

Load Shed - Emergency 

Inhibit

Enables load shed (S2 Inhibit), See 36A

36A

I

Load Shed - Emergency 

Inhibit w Keyed Switch 

Provides a device panel mounted selector switch to initiate a load circuit disconnection from the Source 2 power source. If the load circuit is 

connected to Emergency and the selector switch is switches to the "S2 Inhibit/Enabled" position, then a re-transfer to Source 1 is completed 

if Source 1 is available. If the Preferred Source is not available, then the transfer switch will transfer to neutral. If the load circuit is connected 

to Source 1 and the switch is in the "Emergency Inhibit" position, then a transfer Source 2 is prohibited. 

37

I

Go to "Isolated" Position 

Provides an input to transfer a 3 position transfer switch (source 1/off/source 2) to the off position using a remote contact closure.  When the 

signal is removed, the transfer switch will transfer back to the available, prefrred source.

81J

I

Lockout

Provides an input to temporarily disable automatic control. This feature is used to indicate a tripped breaker in a breaker based transfer 

switch.  It is treated as an alarm and the alarm must be rest to continue automatic operation.

81K

I

Monitor Mode (N.O. or N.C.) Provides an input to disable automatic control in the ATC-900 controller.  This function is used for when manual operation is required.  The 

controller continues to accurately monitor source status and set points can be changed, however no action will be inititated by the controller. 

There are two settings, N.O. and N.C.

81P

I

Contactor Bypass Safety 

Interlock Alarm

Whenever the contactor bypass will not operate automatically because of items as: a Door Open, a Contactor(s) not locked in, not in auto-

matic, in Monitor Mode, etc. Also can be monitored by Mod-bus and Ethernet.

81R

O

Waiting for Sync

Provides an output that closes when closed or in-phase

81S

I

Closed Transition Inhibit

 An input, when closed, will inhibit closed transition.  The transition will now be an open type (depending on what the open set point is set to)

90B

I

Secondary Input 

The ATC-900 Primary/Secondary controller functionality provides the user with the ability to use two independent transfer switches in three 

source systems consisting of a utility and two generator sources. In a three-source system, the Primary ATS controls the engine starting and 

stopping of the Secondary ATS.  The Secondary input receives the engine start signal from the Primary controller.

14C

O

S1 Available

The ATC-900 will measure voltage and frequency and if they are measured in the envelope of the settings an Output will show that S1 is 

Available 

14D

O

S2 Available

The ATC-900 will measure voltage and frequency and if they are measured in the envelope of the settings an Output will show that S2 is 

Available 

15R

O

Normal (S1) Source Position 

1 Form C 

Provides 1 form-c relay contact that indicates the position of the source 1 power switching device.

15S

O

Emergency (S2) Source Posi-

tion 1 Form C 

Provides 1 form-c relay contact that indicates the position of the source 2 power switching device.

35A

O

Pre-Transfer Contacts

Provides a signal prior to the transferring of the load. Will not transfer until the programmable delay set point in the controller is reached. If 

both sources are not available, this option will ignore the time delay set in the controller.

35D

O

Post Transfer Contacts

Provides a signal after the transferring of the load to the delay set point of the controller when reached. 

Summary of Contents for ATC-900

Page 1: ...escription Page 1 Introduction 2 2 Hardware Description 6 3 Operator Panel and Display Menus 12 4 Operation 15 5 Setpoint Programming and I O Programming Using the Color Display 18 6 Troubleshooting a...

Page 2: ...e strict liability or otherwise for any special indirect incidental or conse quential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system co...

Page 3: ...00 4 3 Radiated susceptibility tests IEC 61000 4 4 Fast transient tests IEC 61000 4 5 Surge withstand tests IEC 61000 4 6 Conducted immunity tests IEC 61000 4 11 Voltage dips and interruptions IEC 610...

Page 4: ...ble I Os are covered in Section 5 The only item that is optional for the transfer switch is the closed transition optional feature The closed transition operation is cov ered in section 1 5 3 The swi...

Page 5: ...ust be synchronized in frequency phase and voltage before the transfer is initiated In phase transition is a feature that will allow a transfer between two live sources only when the phase difference...

Page 6: ...liarize the reader with ATC 900 hardware its nomenclature and to list the unit s specifica tions The information presented is divided into the following four parts Operator Panel Rear Access Area Exte...

Page 7: ...er stand LED type 4 Color Display Window easy to read monitored param eters setpoints and messages 5 Bypass Timer used simultaneously to bypass timers such as TDNE TDEN and TDEC 6 Help Pushbutton prov...

Page 8: ...n the controller The DCT is used to measure load current when selective load shed is enabled The DCT Module also has a 24 Vdc input for powering the ATC 900 controller If 120 VAC and 24 Vdc is supplie...

Page 9: ...T 991 Effects of shipping and storage test Thermal cycling test Humidity test UL 1008 Dielectric test FCC Part 15 Conducted radiated emissions Class A CISPR 11 Conducted radiated emissions Class A IEC...

Page 10: ...igure 5 I O Module s Wiring 2 5 3 Ethernet Module Description The Ethernet Communications Module is an optional accessory that operates as a communicating device in conjunction with a the ATC 900 via...

Page 11: ...idity non condensing Enclosure Compatibility NEMA 12 standard mounting NEMA 4 4X mounted with gasket between panel and device faceplate NEMA 3R outdoor UV Resistant ATC 900 Faceplate System Voltage Ap...

Page 12: ...s like the up down left and right Arrows will also continue to scroll if they are pressed and not released 3 3 2 Help Pushbutton When the Help pushbutton is pressed and released with the ATC 900 in an...

Page 13: ...e Diff iv In Phase Transition No Sync to Alarm or Open v Frequency Diff vi Sync Timer vii Time Delay Neutral TDN viii Load Decay d Screen 4 Setpoints Switch Type Settings 4 of 4 2 View Setpoints Time...

Page 14: ...Event Details c Hi Speed Captures d Event Data 8 System Info Figure 7b a Style b Transitions c GO Number d Serial Number e Fixed I O f Firmware Versions g Time Date 9 USB Menu a Save Setpoints b Load...

Page 15: ...ure 2 for a graphical representation and position of all input connections There are two types of I Os programmable and fixed Most I O are programmable by the user at any time There are a few that are...

Page 16: ...t input is de activated Bypass Timers Input This momentary contact will bypass the timer for TDEN TDNE TDN TDES and TDEC By pushing the Help and Enter buttons on the front of the controller Bypass Tim...

Page 17: ...lay Neutral TDN Time Delay Normal Disconnect TDND Time Delay Normal Reconnect TDNR Time Delay Emergency Disconnect TDED Time Delay Emergency Reconnect TDER Pre transfer Delay Signal TD PRE TRAN Post t...

Page 18: ...the communications port Users can reprogram setpoints as well as other parameters Up to four optional I O modules each having four in and four out programmable I Os can be used with the ATC 900 That...

Page 19: ...ements of the Load Note that the DCT module is required to display Load current Watts VAR VA and power factor Other wise only voltage measurements will be shown See Section 2 for the DCT Module specif...

Page 20: ...mmable I O The System Setpoints screen contains normal voltage frequency preferred source CT Ratio communications closed or open and several more After the initial setting of these system setpoints th...

Page 21: ...tenance Manual Automatic Transfer Switch Controller ATC 900 Figure 11 Setting Setpoints All setpoints are set in this way The display gives the user a quick look at not just one setpoint but the whole...

Page 22: ...engine 2 start 259 Minutes 0 03 4A Time delay engine cool off 0 9999 seconds 5 00 7A Time delay engine fail timer 0 60 seconds 0 06 Unbalance phase loss time delay 0 30 seconds 0 20 Any TDES value abo...

Page 23: ...Selective Load Shed General Alarm Indication Contact Monitor Mode ATS in Test Engine Test Aborted Cooldown in Process Engine Start Contact Status Gen 1 2 LOAD SHED Emergency Inhibit On ATS on Bypass L...

Page 24: ...ample When the I O is Fixed the display will show the particular I O in the designated slot The display will show a fixed I O as black instead of blue Table 8 shows the features and the I O of the con...

Page 25: ...ne Test 6B Engine Test Pushbutton on Panel S S S S S S S S S 6C Remote Engine Test INPUT P P P P P P P P P I 7B Time Delay Engine Fail TDEF Adjustable 0 60 Sec S S S S S S S S S Pushbutton Bypass 8E B...

Page 26: ...Transfer Signal Contacts Form C P P P P P P P P P O 36 Load Shed S2 Inhibit INPUT P P P P P P P P P I 36A Load Shed S2 Inhibit w Keyed Switch INPUT OF OF OF OF OF OF OF OF OF I 37 Go to Isolated Posit...

Page 27: ...81F Engine Start Contact Status Gen 1 Gen 2 OUTPUT P P P P P P P P P O 81G LOAD SHED S2 Inhibit On OUTPUT P P P P P P P P P O 81GL LOAD SHED S2 Inhibit On w white indicating light OF OF OF OF OF OF O...

Page 28: ...Stuck waiting for Neutral position ATC 900 is malfunctioning Verify that control power is connected at J7 and that it is within specifications Mechanical problem No inputfrom limit switch Replace the...

Page 29: ...not locked in Statis lamp is on Monitor Mode Unit is in manual mode Close the door s assure contactor s is locked in turn top user switch to auto matic Unit displays Lockout No contact closure at Loc...

Page 30: ...ine voltage and frequency available at ter minals N1 N2 and N3 Record the readings If YES Proceed to Step 4 If NO Check Preferred source Step 4 Is the transformer voltage selector plug in the correct...

Page 31: ...o be present on some of the terminal blocks Step 3 Before disconnecting any wires from the unit make sure they are individually identified to ensure reconnection can be correctly performed Taking a pi...

Page 32: ...removed to when the switch transferred includ ing engine start and source available Historical Data Figure 15 Historical Data Screen The Historical Data display indicates historical and cumulative co...

Page 33: ...splay Insufficient Memory To load controller setpoints from a setpoint file on your USB flash drive use the arrow keys to navigate to the Load Setpoints icon and press Enter The Load Setpoints feature...

Page 34: ...defined period of time TDER with a range of 0 60 seconds A flowchart example is shown in Appendix C Feature System Nominal Frequency NOMF There are only two choices for system nominal frequency of the...

Page 35: ...pushbutton remote switch to any of the Inputs to do the same function This feature is usually used in testing when it is not desirable to wait for completion of the tim ing sequence Feature 9B Mainten...

Page 36: ...bal ance must drop to a value that is below the pickup setting to stop the timer or to become available after the timer expires This can be disabled in the setpoint settings under menu 3 in the Setpoi...

Page 37: ...Source See the Con trol Inputs section for more information The ATC 900 when used in conjunction with the optional DCT metering module has the ability to shed and pick up loads based on available gene...

Page 38: ...er failure of S2 The Generator Fail Alarm remains active until either manually cleared or until Second ary In is removed and re asserted to start a new session Once a generator fails the other generat...

Page 39: ...Source Gen Start Set Emergency Source to Idle state Yes No No Set transfer switch to Emergency Source No TDN or TDNE if switch was previously on Normal Source No Change to Preferred Source Gen Start o...

Page 40: ...C Set Source 2 to Idle state Yes No No Set transfer switch to Source 2 No TDN or TDNE if switch was previously on Source 1 Turn off Source 1 Gen Start after fixed 5 minute TDEC Set Source 1 to Idle st...

Page 41: ...se of Phase Angle 13 Source 1 Mech Failed to Open The Source 1 Mechanism for a breaker or contactor did not open 14 Source 1 Mech Failed to Close The Source 1 Mechanism for a breaker or contactor did...

Page 42: ...1 is not available to switch to neutral 3 Time Delay Normal to Emergency Countdown timer before normal is opened for transfer to emergency source 4 Time Delay Normal Reconnect Countdown timer for whe...

Page 43: ...e manual retransfer feature Selection of this option automatically adds option 29J 36 I Load Shed Emergency Inhibit Enables load shed S2 Inhibit See 36A 36A I Load Shed Emergency Inhibit w Keyed Switc...

Page 44: ...rovides remote indication that the ATS is currently running a test The test could be initiated by the device panel engine test pushbutton or automatically using the programmed engine excersier 81D O E...

Page 45: ...UW WR FRXQWGRZQ DIWHU WKH 6RXUFH PDLQ FRQWDFWV FORVH 7 1 WLPH GHOD H SLUHV 25 9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW ORVH 6RXUFH PDLQ FRQWDFWV DFWXDWH UHOD 6RXUFH LV SRZHULQJ...

Page 46: ...HV ZKHQ SRVW WUDQVIHU FRQILJXUHG 7 WLPH GHOD H SLUHV 5HPRYH QJLQH 6WDUW VLJQDO GH DFWXDWH JHQ VWDUW UHOD 6HQG QJLQH 6WDUW VLJQDO DFWXDWH JHQ VWDUW UHOD 1R HV HV 1R 6 QF WLPH GHOD VWDUWV FRXQWGRZQ DYH...

Page 47: ...9 VDWLVILHG ZKHQ SURGXFW FRQILJXUDWLRQ VXSSRUWV ORDG GLVFRQQHFW HV 1R 3RVW WUDQVIHU WLPH GHOD H SLUHV ZKHQ SRVW WUDQVIHU FRQILJXUHG V IDOOEDFN WR RSHQ LQ SKDVH WUDQVLWLRQ FRQILJXUHG 6 QF WLPH GHOD VW...

Page 48: ...Normal TDND 0 Disconnected from both TDNR Counting Down Normal Available Set TDNR Emergency Available Set TDNE Emergency Unavailable Clear TDNE Normal Available Clear TDND Normal Unavailable Set TDND...

Page 49: ...ailable fail safe transfer TDED Time Delay Emergency Disconnect 0 10 sec TDEN Time Delay Emergency to Normal 0 9999 sec TDER Time delay Emergency Reconnect 0 60 sec Disconnected from both No Timers Co...