Access Power Solutions Installation Guide (APS6-400 Series)
86
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
System Controls
Equipment Required:
DC Load bank
Test
Test procedure
Adjustment
Voltage Control
Note 1
Apply a load to the power system.
With
DCTools
, ensure the bus voltage matches the
Target
Voltage
as shown on the Voltage Control Summary of
DCTools
.
None
Temperature
Compensation
Note 2
Heat the battery temperature sensor.
Ensure the system voltage changes in accordance with the
configured slope.
None
Equalize
Set the
Equalize Duration
to 1 minute.
Start an
Equalize
.
Ensure the system voltage increases to the
Equalize Voltage
.
Ensure the SC200 or SC100 indicates an
Equalize
has
started.
Ensure the
Equalize
stops after the 1 minute duration.
Return the
Equalize
duration to the original setting.
None
Fast Charge
Note 3
Set the
Fast Charge Max Duration
to 1 minute.
Set the
Fast Charge Voltage Threshold
to a value
approximately 1V below the system float voltage.
Connect load to the system.
Turn off the ac to the system.
Allow the system voltage to fall below the
Fast Charge
Voltage Threshold.
Turn on the ac.
Ensure the system performs a
Fast Charge.
Ensure the SC200 or SC100 indicates a
Fast Charge
has
started.
Ensure the
Fast Charge Voltage
is correct.
Ensure the
Fast Charge
stops after 1 minute.
Return the
Fast Charge
settings to the original values.
None
Generator Control
Option
(SC200 only)
Note 4
Set the
Voltage Threshold
to a value approximately 1V below
the system float voltage.
Connect load to the system.
Turn off the ac to the system.
Allow the system voltage to fall below the
Voltage
Threshold.
Ensure the system performs a
Fast Charge.
Ensure the SC200 indicates a
Generator Enable
.
Ensure the
Generator Enable
digital output activates.
Turn on the ac.
Ensure the
Generator Enable
stops after 1 minute.
Return the settings to the original values.
None
Battery Current
Limit
Note 5
Reduce the
Battery Current Limit
setting to 5%.
Connect load to the system.
Turn off the ac to the system.
Allow the battery to discharge for a period.
Turn on the ac.
None