LVD Specifications APS6-400
Low Voltage Disconnect (LVD) Contactors
Battery Disconnect
400A
Low-priority Load Disconnect
200A
In APSs without an internal battery disconnect LVD, either the total battery current must be less
than 285A or the APS must be protected by an external battery LVD set to 43V or higher.
Fuses
Rectifier (internal) ac input fuses (F1, F2)
16A, 250Vac, fast acting
Rectifier (internal) auxiliary fuse (F3)
250mA, 250Vac, fast acting, interrupt rating 1500A
min.
Environment
Ambient Temperature Range:
-40°F to 113°F [-40°C to 45°C]
Relative Humidity
(operating and storage)
<95% (non condensing)
Dimensions H, W, D
APS6-400
6U, 19" or 23" mounting, 15.3" [390 mm]*
* Additional clear air space is required at rear for rectifier exhaust air venting. See details on page
Weight
APS6-400
46.3 lb [21kg]*
Rectifier module
3.7 lb [1.7kg]
* weight of a typical configuration, excluding rectifiers
Digital Outputs/Alarm Relays (IOBGP)
Number of Digital Outputs/Relays
6 (one also used for Monitor OK alarm)*
Contact Arrangement
One changeover contact per relay
Contact Rating
0.1A @ 60V dc maximum
Connectors
Screwless terminal blocks
Wire Size
0.5 - 2.0mm
2
[20 - 14 AWG]
Isolation
Relay connections are isolated to 500V dc from all
other circuitry, earth and system common.
* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board
loses power or loses communication with the SC200 or SC100.