Access Power Solutions Installation Guide (APS6-400 Series)
84
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
Analog Inputs
Equipment required:
Digital Voltmeter
DC Load bank
DC Current Clamp meter
Trim pot adjustment tool
Thermometer
Test
Test procedure
Adjustment
DC Voltage
Measure the dc voltage across the dc bus.
Ensure the bus voltage on the SC200 or SC100 display and
in DCTools/Web is within specifications.
None
Battery Current
(High current test)
Note 1
Conduct the load test and turn off the rectifiers.
Measure the load current with a dc clamp meter.
Ensure the current displayed on the SC200 or SC100 and in
DCTools/Web is within specification.
Ensure the current is the correct polarity.
Adjust the gain setting on
the current sensor by
moving the trim pot.
Adjust the gain setting in
the SC200 or SC100
Load Current
(High current test)
Note 2
Connect a load bank to the dc load connection
Apply a high load to the system
Measure the load current with a dc clamp meter
Ensure the load current displayed on the SC200 or SC100
and in DCTools/Web is within specification.
Ensure the current is the correct polarity.
Adjust the gain setting on
the current sensor by
moving the trim pot.
Adjust the gain setting in
DCTools/Web.
Total System
Current
(High current test)
Repeat the load test.
Ensure the system current displayed on the SC200 or
SC100 and in DCTools/Web is within specification.
None
Load Current
(No current test)
Disconnect the load bank from the system.
Ensure the load current displayed on the SC200 or SC100
and in DCTools/Web is 0 amps.
Adjust the current offset
setting of the SC200 or
SC100.
Battery Current
(No current test)
Disconnect the load bank from the system.
Ensure the battery current displayed on the SC200 or
SC100 and in DCTools/Web is 0 amps.
Adjust the current offset
setting of the SC200 or
SC100.
Total System
Current
(No current test)
Disconnect the load bank from the system.
Ensure the total system current displayed on the SC200 or
SC100 and in DCTools/Web is 0 amps.
None
Temperature
With thermometer, measure the temperature at the power
system temperature sensor.
Ensure the temperature input displayed on the SC200 or
SC100 and in DCTools/Web is within specification.
Test each temperature input.
Some temperature sensors
have an adjustable trim
pot.
User assigned
Analog Inputs
Note 3
Test the accuracy and alarm mapping for all analog inputs.
Check the name, severity and alarm thresholds are correct.
See Note 3.