Installation
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
33
AC terminals (4 used for two feeds, 6
used for three feeds)
Ground stud (M6)
Step 4 - Replace ac terminal cover
Step 5 - Connect at the ac supply point
1
Check the ac supply point is isolated.
2
Connect the conduit wires to the ac supply point, as required.
Follow the manufacturer's instructions and local wiring regulations.
3
Label the connection at the ac supply point.
Step 4 - Check terminations, secure cable and test insulation
1
Check all terminations are correct and are tightened.
2
Secure the cord(s) or cable to ensure there is no strain on the terminals.
3
Test the insulation resistance of the conductors according to local ac wiring
regulations.
Procedure complete
Installation Completed
Installation of the APS is now complete. Follow the instructions in Start-Up on page
the system operational.