Access Power Solutions Installation Guide (APS6-400 Series)
62
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
4
On the SC200 go to: Battery > LVDs > LVD x > Not Characterized > Edit, or on
the SC100 go to: Menu > Configuration > LVD1/LVD2
Select
Characterize
. Press
Enter/Save
.
The LVD contactor will disconnect and connect.
Repeat for the second LVD if fitted.
Procedure Complete
Return the faulty SC200 or SC100 with a completed Equipment Incident Report on page
Replacing the Input/Output Board
When the I/O board is removed any LVD fitted will disconnect:
If a battery disconnect LVD is fitted the battery will be disconnected when the I/O
board is removed (the load equipment will continue to operate from the rectifiers).
If a load disconnect LVD is fitted then the equipment connected to circuit breakers 1-
10 will be disconnected when the I/O board is removed.
Before you start you will require:
A PC/Laptop with
DCTools*
connected to the system controller or (SC200 only) a web
browser* connected to the system controller via an IP network.
*See Communications Options in the System Controller Operation Handbook.
A replacement input/output board.
An anti-static wrist strap to prevent damage to the static sensitive components on the
input/output board.
Step 1 - Load disconnect LVD (if fitted)
Ignore this step if there is no load disconnect LVD fitted.
If a load disconnect LVD is fitted then load equipment connected to circuit breakers
1-10 will be disconnected. Either, arrange to switch off this equipment or connect a
temporary external power source to power the equipment when the load LVD
disconnects.
Step 2 - Remove cover to access I/O board
1
2
Remove the Input/Output (I/O) cover.