Access Power Solutions Installation Guide (APS6-400 Series)
20
Copyright © 2009-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-53B December 2010
1
Remove the access panel on the side of the APS.
2
Either:
To fit the battery LVD contactor:
Undo the two bolts and remove the link bar.
Fit the two pieces of bus work. Tighten the M8 bolts to 9.5 - 11.1Nm (85 - 98
inch-pounds).
Fit the contactor and tighten the M10 nuts to 18.7 - 21.9Nm (166 - 194 inch-
pounds).
Connect the contactor control cable to the contactor.
Or, to remove the battery LVD contactor:
Disconnect the contactor control cable from the contactor.
Undo the two nuts and remove the contactor.
Undo the two bolts and remove the two pieces of bus work.
Fit the link bar and tighten the M8 bolts to 9.5 - 11.1Nm (85 - 98 inch-pounds)
3
Replace the access panel.
Step 5 - Fit or remove the low-priority load disconnect LVD (if required)
Load disconnect LVD contactor.
Link bar (in place of contactor).