User Manual 200 kVA-1200 kVA UPS
8
Technical Parameters
81
8 Technical Parameters
8.1 Models
Rated capacity
Frequency
Rated capacity
Frequency
200 kVA/200 kW
50/60 Hz
600 kVA/540 kW
50/60 Hz
250 kVA/250 kW
50/60 Hz
750 kVA/750 kW
50/60 Hz
300 kVA/270 kW
50/60 Hz
900 kVA/810 kW
50/60 Hz
400 kVA/400 kW
50/60 Hz
1000 kVA/1000 kW
50/60 Hz
500 kVA/500 kW
50/60 Hz
1200 kVA/1080 kW
50/60 Hz
8.2 Single Module
8.2.1 UPS System Input
Input
Parameters
Input phase number
Three phase five wires (3Φ+N+PE)
Rated input voltage
380/400/415 Vac
Variable range of input voltage
260 ~ 460 Vac
Variable range of input
frequency
40 ~ 70 Hz
Input power factor
≥ 0.99
Battery voltage
480 Vdc (456/468/492/504 Vdc optional)
Cell number
12 V x 40 cells (38/39/41/42 optional)
8.2.2 UPS System Output
Output
Parameters
Output phase number
Three phase five wires (3Φ+N+PE)
Rated output voltage
380/400/415 Vac
Output voltage regulated
accuracy
≤ 1%
Accuracy of output frequency
Mains mode: synchronous state, tracking bypass input 50/60hz;Battery
mode: 50/60 Hz ± 0.05%
Inverter overload capacity
100% < Load ≤ 105% overload alarm, loading for long term
105% < Load ≤ 110% switch the bypass after 60 minutes
110% < Load ≤ 125% switch the bypass after 10 minutes
125% < Load ≤ 150% switch the bypass after 1 minutes
150% < Load switch the bypass after 0.2s