User Manual 200 kVA-1200 kVA UPS
5 Operation
76
Step 2
:
Disconnect the output switch of the UPS to be maintained.
Step 3
: Disconnect the battery switch of the UPS to be maintained (if there are multiple battery packs, disconnect
the main switch between the battery pack and the UPS first, and then disconnect the switch of each battery pack).
Step 4
: Disconnect the mains input switch and bypass input switch of the UPS to be maintained.
Step 5
: The UPS to be maintained is isolated from the system after the completion of Step 4, and the maintenance
operation can be performed after the capacitor voltage falls below the safe voltage.
5.9.5 Add a Single UPS After Maintenance
Operation procedures:
Step 1
: After UPS maintenance is completed, close the mains input switch, bypass input switch, output switch and
battery switch of UPS.
Step 2
: Confirm that the option of [Single/Parallel] in the basic parameter setting is set to [Parallel] according to
Step 5.1, power on the equipment in the LCD panel.
Step 2
: After the added UPS is fully started, the added UPS should share the load equally with other UPS of in the
parallel system, and confirm whether the load of the UPS shown in energy flow diagram of the home is consistent
with that of other UPS. If so, it means that the process of adding the single UPS after the maintenance has been
completed.