User Manual 200 kVA-1200 kVA UPS
3 Installation
17
3. 1. 3 Preparation of Power Cables
Recommended cable diameters for UPS power cables are shown in Table 3-4, and requirements for power cable
bolts are shown in Table 3-5.
Table 3-4 Recommended cable diameters for power cables
Item
200 kVA
250 kVA
300 kVA
400 kVA
500 kVA
Mains
input
Mains input current (A)
332
414
452
664
828
Recommended cable
diameter (mm
2
)
A/B/C/N
1×120
1×185
1×185
2×120
2×185
Recommended
terminal
A/B/C/N
DT120-14
DT185-1
6
DT185-16
DT120-14 DT185-16
Bypass
input
Bypass input current (A)
290
361
434
607
759
Recommended cable
diameter (mm
2
)
A/B/C/N
1×120
1×150
1×185
2×120
2×150
Recommended
terminal
A/B/C/N
DT120-14
DT150-1
4
DT185-16
DT120-14 DT150-14
Output
Output current (A)
290
361
434
580
722
Recommended cable
diameter (mm
2
)
A/B/C/N
1×120
1×150
1×185
2×120
2×150
Recommended
terminal
A/B/C/N
DT120-14
DT150-1
4
DT185-16
DT120-14 DT150-14
Battery
input
Nominal discharge current (A) of
4 x 12V battery
448
559
605
896
1118
Recommended cable
diameter (mm
2
)
BAT+/BA
T-
1×185
2×95
2×95
2×185
2*240
Recommended
terminal
BAT+/BA
T-
DT185-16
DT95-12
DT95-12
DT185-16 DT240-16
Ground
wire
Recommended cable
(mm
2
)
PE
1×70
1×70
1×95
1×150
1×185
Recommended
terminal
PE
DT70-12
DT70-12
DT95-12
DT150-14 DT185-16
Item
600 kVA
750 kVA
900 kVA
1000 kVA 1200 kVA
Main
Mains input current (A)
904
1242
1356
1656
1808
Recommended cable
diameter (mm
2
)
A/B/C/N
2×185
2×185
3×240
4×240
4×300
Recommended
terminal
A/B/C/N
DT185-16
DT185-1
6
DT240-16
DT240-16 DT300-20
Bypass
input
Bypass input current (A)
868
1083
1302
1444
1736
Recommended cable
diameter (mm
2
)
A/B/C/N
2×185
3×150
3×240
4×240
4×300
Recommended
terminal
A/B/C/N
DT185-16
DT150-1
4
DT240-16
DT240-16 DT300-20