Condensation Water Drain Connection
INFORMATION
The electrical connection cable of the appliance must be supplied in a grounded power supply line
which can provide enough voltage for the appliance (230V AC, 50Hz). Controlboard faults caused by
voltage fluctuations and absence of grounding and damage that may occur to your appliance are not
covered by the warranty.
WARNING:
Care must be taken to ensure that there is abso
-
lutely no voltage on the power line when the electrical connec
-
tion of the appliance is being done.
Always connect your appliance to a 230V AC, 50Hz grounded
power outlet. If the supply cable is damaged, it must be
replaced by E.C.A authorized services.
A 2 amp bipolar fuse with a minimum contact opening of 3mm
must be used in the electrical connection of the combi boiler.
Electrical Connection
• • In condensation combi boilers, condensation occurs during combus
-
tion. The amount of condensation water differs according to the operating
conditions of the appliance.
- The condensation water must be connected to a drain by means of a plastic hose which is connected
to the end of the siphon. The use of standard drain hose is recommended for connection to the
drain. The addition of 1 cable tie on the hose must be made for fixing.
- If the drain hose is to be connected to a drain from the outside of the building, it should be insulated
if it is necessary for the hose not to freeze.
- The condensation water drain hose and interconnection parts must be made of plastic material.
- All horizontal hose connections must be downwardly bent by 2° or 3° to ensure good flow through
the drain hose.
17