Room Sealed Type Flue Connections
Our combi boilers have the following room sealed flue connection options:
1. Horizontal flue connection (Ø60 / 100 mm) max. Up to 3 meters
2. Vertical flue connection (Ø60 / 100 mm) max. Up to 4 meters
If an elbow is used in the flue connections, the lengths are always reduced by 1 m when using a 90°
elbow or two 45° elbows. Up to two 90° elbows can be used. (Figure 7)
2
3
2
11
Sample flue installation with single 90˚ elbow
Sample flue installation with two 90˚ elbows
Sample flue installation with single 90˚ elbow and 45˚ elbow
Figure 7