13 of 3
1) The root directory has two folders: EVAC-related message and chimes message.
2) The voice file in the “alert_message” and “evac_message” in the EVAC folder is defaulted as one audio file
respectively while they are delivered from the factory. The user can add or delete it according to the actual needs,
and the host will detect it in a real-time manner; the log message of current system modules is stored in the LOG
folder, and it can be classified and checked or stored as the spreadsheet file via the PAVA6500 (Please refer to
PAVA6000);
3) The bell voices before and after the paging of the user are stored in “Prompt” Folder, namely, the prompt tone.
The user can configure different bell tone for each PAVA6006 according to the actual needs. What’s different from
the EVAC voice message is that the bell message of this file will not be detected in a real-time manner and it can be
read only once. No file or file damage may cause no output of bell tone during the paging process. The fault of the
device will not be reported and no record will be made.
4) After the folder in the SD card is formatted, the host will automatically build the corresponding folder.
However, the EVAC voice message and bell tone will not be automatically saved and restored, and the user shall
pay attention to the backup measures to avoid the loss of message while replacing and formatting the SD card.
5) The number of three audio files stored in the folder shall not exceed 255. When it exceeds this number, only
255 audios are valid.
○
,10 /
○
,11 —— Backup Power Amplifier Interface
”10” power signal inputs;
“11” audio signal output. Attention shall be paid to that it is a balanced output herein.
○
,12 —— Relay Fault Status Output Interface of the System
In case of any fault for the system, this output interface is disconnected and conversely it is closed.
○
,13 —— Relay Fault Output Interface for System Operation Status
When the system works in a fire status, this output interface is closed and otherwise it is disconnected.
○
,14 —— Fire Reset Input Interface (greater than or equal to 0.5S relay short-circuit
input, used to connect CIE device and realize the on-line control)
When the current equipment works in a fire mode, reset it to switch into a normal mode.
When it is operated in a normal mode, it is not processed and ignored.
○
,15 —— Host Module Configuration Switch (UP means “ENABLE” and DOWN means
“DISABLED”)
“1” represents the total detection ID of system equipment, and when it is in “ENABLE”, it means that the user
allows the equipment to monitor the operating status of various modules, and otherwise, it is “DISABLED”;
“2” represents DC24V power supply configuration ID. When it is in “ENABLE”, it means that the system is
provided with the DC24V power supply, and the user is required to connect the 24VDC power supply at “1” and
otherwise, it is “DISABLED”; it will be OK to suspend the DC24V wiring ports;