11 of 3
○
,1 —— DC24V DC Power Input Jack (Interface)
The DC24V power supply to be connected can be the sealed lead-acid batteries, UPS or their similar products.
Notes:
1. If an EN standard shall be adopted, please confirm that the power supply complies with the Standard EN54-4.
2. Please confirm that DC24V power supply can provide the minimum operating current for the rated output of
PAVA6500 (take the combination of PAVA6500 with the sealed lead-acid battery for example: if it works in the full
load, the output current provided shall not be less than 27A, namely, power capacity shall not be less than 27Ah, and
the operating time is: <full load operation *27Ah*1.2> hour).
○
,2 —— 6 DC24V Output Interfaces
Connect four-wire audio control system;
The rated output current is 0.2A for each line.
Note: the total output power of the six lines may not be greater than 28W.
○
,3 —— 6 Speaker A&B Circuit Output Interfaces
Connect the constant pressure speaker or 3-wire audio control system;
Output voltage is 0-100V.
Note: please make at least one modeling of the speaker circuit after completing the wiring. It will be OK to suspend
the partition that is not connected with the speaker. Of course, its output can also be prohibited in PAVA6000 (the
related operations refer to the related chapters of PAVA6000).
○
,4 ——8 Programmable Linkage Relay Output Interfaces
Under the normal status, Output 2 is normally open. Its output status can be decided by the input status of “5” in
PAVA6000, and its output status can be controlled manually in PAVA6000.
Notes: when the linkage relay is controlled by multiple input statuses, its outputs belong to an adding relationship.
For example, the contact 1 of “5” is configured to open the output interface 1, and it does not select the output
interface 2. However, contact 4 of “5” has selected the output interface 2, but it does not select the output interface 1.
The output interfaces are 1 and 2 when they occur simultaneously.