5
English
A p o l l o
80 -
i n s t r u c t i o n
f o r
i n s tA l l At i o n
6.4 Positioning the appliance
Positionthefireasfollows:
N.B.
- Keep combustible objects and/or materials at a minimum distance of 500 mm from the appliance.
- Do not adjust the appliance in any way.
➠
Determine the position of the appliance;
➠
Create a gas connection in the appropriate position; see section 6.3 for details;
➠
Create a duct for the fl ue / combustion air supply system, with the diameter shown below; see section 6.5 for details;
➠
Ø160 mm for a wall duct of incombustible material;
➠
Ø 250 mm for a wall duct of combustible material;
➠
Ø160 mm for a roof duct of incombustible material;
➠
Ø 250 mm for a roof duct of combustible material.
!N.B.
- Allow for the depth of the appliance (see
Fig. 2
) (The minimum depth at the Apollo is 450 mm);
- Allow for the build-in height; this will depend on the height of the adjustable feet (see
Fig. 1a
).
➠
Move the appliance into its intended position.
Thegascontrolblockismountedontotheburnerplateatthebottomoftheappliance.Thisshouldberemovedand
placedinthecontrolboxlater.Seesection6.7forinformationonhowtofitthegascontrolblock.
Commenceasfollows:
➠
Disconnect the hoses from the gas control block (fl exible gas hose, aluminium pilot pipe and thermocouple 1);
Caution
The red wire of thermocouple 2 must remain connected to the gas control.
Fig. 1b
shows how the wires are connected
to the thermocouple.
➠
Unscrew the self-tapping screw in the burner plate and remove the gas control block.
➠
Carefully unwind the red and black wires of thermocouple 2.
➠
Lay the gas control together with the wires of thermocouple 2 in the direction of the control box.
N.B.
- Avoid dirt in the hoses;
- Avoid kinks in the hoses.
➠
Unroll the hoses towards the control box;
➠
Unroll the ignition wire towards the control box.
Apollo 80
Front view
Top view
Side view
50
min. 910 max. 935
995
813
15
448
192
504
min. 160 max. 185
Fig. 1a
min 1450 mm inside
min 450 mm inside
=
=
Control box
38c-1294
max 100 mm
508
817
min
150 mm
min
1350 mm
inside
Total
ventilation
200 cm
2
b
c
Maximal
plaster line
Maximal
plaster line
b
c
A-A
A
A
Fig. 2
Fig. 1b
UK