7
English
A p o l l o
80 -
i n s t r u c t i o n
f o r
i n s tA l l At i o n
Toinstalltheconcentricsystemcommenceasfollows:
➠
Construct the system from the (connection stub of the) appliance up.
N.B.
- Maintain a distance of at least 50 mm between the outside of the concentric system and the walls and/or the ceiling;
If the system is built-into a cove for example, incombustible material should be applied all around;
- Use heat-resistant insulating material for ducts made of combustible material;
- The rosette (mounting inner plate) of the wall duct is too small to seal the Ø 250 mm opening when passing through
combustible material. That is why you should first apply a sufficiently large heat-resistant intermediate plate to the
wall. Then, the rosette is mounted on the intermediate plate.
➠
Connect the concentric pipe sections and the bend(s);
➠
Fit a clamping strip and silicone sealing ring to every connection;
➠
Secure the clamping strip with a self-tapping screw in places which will be inaccessible after installation;
➠
Use enough brackets to ensure that the weight of the pipes does not rest on the appliance;
➠
Determine the remaining length of the wall duct;
➠
Cut the wall duct to size;
!N.B.
- Make sure that the right insertion length is maintained;
- Place the wall duct with the groove/folded seam at the top;
- Make sure the horizontal concentric pipe pieces are sloping towards the wall duct, in order to prevent rain water
from entering.
➠
Mount the rosette (mounting inner plate); if necessary, on a heat resistant intermediate plate when passing through
combustible material;
➠
Attach the wall duct from the outside with four screws in their respective holes.
!N.B.
Some heat-resistant isolation materials contain volatile components that will spread an unpleasant smell for a pro-
longed time; these are not suitable.
6.5.3 Application with roof duct
6.5.3.1 Construction of concentric system with roof duct
Theconcentricsystemwithroofducthastocomplywiththefollowingconditions
➠
The construction of the chosen system has to be allowed. (See the procedure described below);
➠
First, a concentric pipe of at least 1 meter should be connected vertically to the appliance.
Dependingontheconstructionoftheconcentricsystem,theapplianceissetbyplacingthebaffleand/orremoving
theairinletguides.
Inthefollowingprocedureyoucanseehowtheallowabilityofaconcentricsystemcanbedeterminedandwhich
settingsareneeded.
➠
Determine the following data:
1.Thenumberofbendsrequired(nodistinctionismadebetween45°and90°bends);
2.Thetotalnumberofmetersofhorizontalpipelength;
3.Thetotalnumberofmetersofverticaland/orslopingpipelength(wallductnotincluded).
WiththesedataandTable1youwillbeabletodeterminewhethertheconcentricsystemisallowed.
InTable2youcanseewhichsettingtheapplianceneeds.
Followtheproceduredescribedbelow:
➠
In the first 2 columns of Table 1, look for the number of bends required and the total horizontal pipe length;
➠
In the 3rd column of Table 1, look for the total vertical and/or sloping pipe length.
IfyouendupinaboxwiththeletterA,B,C,DorEtheconcentricsystemchosenbyyouisallowed.
➠
Use Table 2 to determine which conditions apply for the baffle and/or the air inlet guides (for setting see section 6.8);
Examples
Toclarify,wewillgive2examplestodeterminetheallowabilityofaconcentricsystemandtheconditionsforsetting
theappliance.
InTable1theroutetobefollowedisindicatedbyarrows.Theresultisindicatedbymeansoftheredframeofthebox.
Example 1
1)2bends
2)3metershorizontal
3)8metersvertical/sloping
→
Constructionofthisconcentricsystemisallowed.
→
SituationBappliesforsettingtheappliance
UK