background image

29

VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION

RO/DI WATER SUPPLY PIPING

The RO/DI-water Vaporstream humidifi er controls water level with a fl oat valve. 
The pipe connection is a 1/4" pipe thread (DN8), except for Vaporstream 
humidifi ers in Europe, which have a 3/8" pipe thread (DN10) connection. 

With the end-of-season drain option, a solenoid valve is added on the inlet 
of the fl oat valve. The end-of-season feature shuts off the fi ll water supply and 
drains the tank when there is no demand for humidity for 72 hours. (This 
length of time is a default setting and is user-adjustable. See the 

Vapor-logic 

Installation and Operation Manual

 for more information.)

When using nonmetallic tubing for supply water, it must be rated for 212 °F 
(100 °C) minimum continuous operating temperature. DriSteem recommends 
installing 3' (914 mm) of non-insulated stainless steel pipe directly off the 
humidifi er (between the humidifi er and the nonmetallic tubing).

If using nonmetallic supply water tubing, DriSteem recommends making a 
2"  (50 mm) water seal or loop in the supply line to isolate steam from the 
nonmetallic tubing. See Figure 23-1.

DriSteem recommends installing a strainer in the water supply line to prevent 
clogging of the fl oat valve orifi ce. A strainer is highly recommended when 
the humidifi er has the end-of-season drain option. The strainer will prevent 
particulate from collecting at the solenoid valve seat.

 WARNING

Fire hazard

Do not supply a RO/DI-water 
Vaporstream humidifi er with tap water. 
Particulates from tap supply water will 
accumulate on and clog the low water 
cutoff switch in the fl oat valve assembly, 
causing a critical safety circuit to fail. 
This can cause a dry tank fi re and 
severe personal injury or death.

Water supply

Piping:

Summary of Contents for Vaporstream

Page 1: ...VAPORSTREAM Electric Humidifier Installation Operation and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS ...

Page 2: ...his manual before performing service or maintenance procedures on any part of the system Failure to follow all warnings and instructions could produce the hazardous situations described resulting in property damage personal injury or death Failure to follow the instructions in this manual can cause moisture to accumulate which can cause bacteria and mold growth or dripping water into building spac...

Page 3: ...onding to a call for humidity during maintenance severe bodily injury or death from electric shock could occur To prevent such start up follow the procedure below before performing service or maintenance procedures on this humidifier after the tank has cooled down and drained 1 Use Vapor logic keypad display to change control mode to Standby 2 Shut off all electrical power to humidifier using field i...

Page 4: ...ning documents from our web site or from DriCalc is the quickest way to view our literature or we will be happy to mail literature to you WARNINGS AND CAUTIONS ii OVERVIEW 2 SPECIFICATIONS 4 North American models capacities and electrical specifications 4 Dimensions 6 Weights and cabinet sizes 8 Selecting a location 9 INSTALLATION 9 Mounting 10 Support legs 10 Overview 10 Trapeze hanger 11 Wall br...

Page 5: ...nformation Download DriSteem literature Most DriSteem product manuals can be downloaded printed and ordered from our web site www dristeem com mc_052410_1335 OPERATION 60 Start up procedure 60 Start up checklist 61 MAINTENANCE 62 Tap softened water 62 Water quality and skim duration 62 Cool down procedure 63 Inspection and maintenance 64 RO DI water option 66 Cool down procedure 66 Inspection and ...

Page 6: ...em supply water guidelines Chlorides RO or DI water Softened water Tap water Damage caused by chloride corrosion is not covered by your DriSteem warranty 5 ppm 25 ppm 50 ppm Total hardness Tap water 500 ppm pH RO DI or softened water Tap water 7 to 8 6 5 to 8 5 Silica 15 ppm You may wish to take action to mitigate potential negative effects to your humidifier Supply water outside of these guideline...

Page 7: ...valve and low water cutoff switch Float ball VLC OM 026 Fill valve opens when water level is below this probe Low water cutoff Power to heaters is cut if water level drops below this probe Fill valve closes when water level rises to this probe mc_030910_1335 mc_030910_1336 WATER TYPE CONVERSION Vaporstream tap softened water humidifiers can be converted in the field for use with RO DI water and Vapo...

Page 8: ...0 43 3 37 5 21 7 17 3 18 27 3 77 0 34 9 9 3 129 8 112 5 97 5 56 3 45 0 74 9 65 0 56 3 32 5 26 0 27 36 3 102 6 46 5 9 3 130 0 75 0 60 0 99 9 86 6 75 0 43 3 34 6 36 48 3 136 8 62 1 9 3 100 0 80 0 133 2 115 5 100 0 57 7 46 2 48 63 3 179 6 81 5 9 3 131 3 105 0 131 3 75 8 60 6 63 75 3 213 8 97 0 9 3 125 0 90 2 72 2 75 24 4 68 4 31 0 12 4 115 4 100 0 86 6 50 0 40 0 66 6 57 7 50 0 28 9 23 1 24 36 4 102 6...

Page 9: ...0 2 6 2 50 72 2 64 6 18 3 9 3 16 5 71 9 21 4 18 26 0 23 3 27 3 9 3 24 8 107 8 32 1 27 39 0 34 9 36 3 9 3 33 1 143 8 42 7 36 52 0 46 5 48 3 9 3 48 69 3 62 1 63 3 9 3 63 90 9 81 4 75 3 9 3 75 108 3 97 0 24 4 12 4 22 0 95 8 28 5 24 34 6 31 0 36 4 12 4 33 1 143 8 42 7 36 52 0 46 5 48 4 12 4 44 2 191 7 56 6 48 69 3 62 1 64 4 12 4 64 92 4 82 7 84 4 12 4 84 121 2 108 6 100 4 12 4 100 144 3 129 3 Heater s...

Page 10: ...x 7 d 508 h x 508 w x 178 d 55 25 L 24 h x 24 d x 7 d 610 h x 610 w x 178 d 73 33 XL 30 h x 24 w x 9 d 762 h x 610 w x 229 d 91 41 XXL 36 h x 30 w x 9 d 914 h x 762 w x 229 d 136 62 Weight does not include humidifier mc_021010_0555 mc_030410_0900 Dimensions FIGURE 6 1 VAPORSTREAM DIMENSIONS TAP SOFTENED WATER AND RO DI WATER Table 6 2 Control cabinet weights for European models Cabinet dimensions W...

Page 11: ...4 4 84 4 100 4 44 72 1136 22 00 559 18 88 480 Vaporstream model kW stages With mounted control cabinet option Max control cabinet size A length 2 B width 2 C height 2 inches mm inches mm inches mm 2 1 3 1 4 1 5 1 M 21 22 539 34 00 864 30 31 770 6 1 9 1 12 1 16 1 21 1 25 1 M 26 90 683 30 00 762 30 31 770 12 2 18 2 24 2 32 2 42 2 50 2 L 30 90 785 30 00 762 34 11 866 18 3 27 3 36 3 48 3 63 3 75 3 XXL...

Page 12: ... L L L L L 32 2 79 36 237 108 L L L L L L L 42 2 79 36 237 108 L L L L L 50 2 79 36 237 108 L L L 18 3 110 50 326 148 L L L L L L L L L L 27 3 110 50 326 148 XL L L L L L L L L L 36 3 110 50 326 148 XL L L L L L L L 48 3 110 50 326 148 L XXL XL L L L L 63 3 110 50 326 148 XL XXL L L L 75 3 110 50 326 148 XXL L XXL 24 4 153 70 427 194 L L L L L L L L L L 36 4 153 70 427 194 XL XL XL L L L L L L L 4...

Page 13: ...on of this manual Water seal requirements see Piping section of this manual Avoid locations above critical equipment or processes Avoid locations close to sources of electromagnetic emissions such as power distribution transformers and high horsepower motors controlled by variable frequency drives Selecting a location Top 18 457 mm Right side 6 152 mm Floor 24 610 mm Front 36 914 mm Cleanout plate...

Page 14: ...Weather cover X X Outdoor Enclosure X X mc_022310_1354 VLC OM 006 Optional set of four legs and hardware INSTALLATION Mounting SUPPORT LEGS Support legs are not available for single heater models 2 1 3 1 4 1 and 5 1 These models must be mounted with a trapeze Page 11 or an Outdoor Enclosure Pages 14 through 21 Use enclosed bolts nuts and washers to fasten legs to tank Shim or adjust so the tank se...

Page 15: ...in this document Overhead installation Do not install water piping and humidifiers above expensive apparatus or equipment A broken water pipe leaking valve gland condensation or other water leaks can occur causing serious damage and costly repairs to the equipment below If this type of installation cannot be avoided install a drip pan constructed of galvanized sheet metal under the humidifier to cat...

Page 16: ...ter and nine heater models lag bolt coach screw to three studs 12 heater models lag bolt coach screw to four studs Lag bolt coach screw wall brackets to the horizontal 2 4s 100 mm 50 mm timbers Locate the wall brackets so they are flush to the front and back flanges of the tank Metal stud wall follow the same 2 4 wood stud 100 mm 50 mm timber wall guidelines but provide a second set of 2 4s 100 mm 5...

Page 17: ...in access to the Vaporstream for service and maintenance ANNUAL WEATHER COVER MAINTENANCE REQUIREMENTS Check all fasteners and verify they are secure Check for any sign of leakage trace back to origin and repair mc_022510_1235 Installation notes Open the hinged doors to make necessary connections to the humidifier Refer to the installation section of this manual for all electrical supply water and ...

Page 18: ...ns Letter Description 1 heater and 3 heater covers 6 heater cover 9 heater cover 12 heater cover inches mm inches mm inches mm inches mm A Height 66 1676 66 1676 66 1676 66 1676 B Length 44 1118 44 1118 44 1118 44 1118 C Width 35 889 39 991 44 1118 50 1270 D Distance from bottom 6 152 6 152 6 152 6 152 OM 7434 D B C A INSTALLATION Note Weather Covers are only available in the United States and Can...

Page 19: ...9 12 heaters Run the electrical power into the enclosure at these knockouts 3 All piping from the Vaporstream unit to the steam outlet is stainless steel pipe Depending on the application interconnecting piping from the steam outlet to the dispersion assembly can be tubing or DriSteem steam hose See the Dispersion section of this document for more information about connecting to the dispersion ass...

Page 20: ... optional heater J Control cabinet Note Some 9 12 heater models have control cabinet mounted on humidifier mc_030410_1505 Table 16 1 Vaporstream Outdoor Enclosure dimensions Item Description Vaporstream models with 1 6 heaters with 9 12 heaters inches mm inches mm A Enclosure height 56 00 1422 56 00 1422 B Enclosure width 40 00 1016 54 00 1372 C Pipe chase position 2 50 67 2 50 67 D 2 50 64 2 50 64...

Page 21: ...48 3 63 3 75 3 9 860 390 1090 494 24 4 36 4 48 4 64 4 84 4 100 4 12 910 413 1190 540 Includes humidifier mc_030410_1100 Table 17 3 Vaporstream Outdoor Enclosure connection sizes Description All Vaporstream models Water makeup fill 1 4 pipe thread DN8 Drain 3 4 DN20 Condensate return 3 4 pipe thread DN20 mc_030410_1101 Table 17 2 Vaporstream Outdoor Enclosure electrical specifications Voltage Current...

Page 22: ...g See Figure 18 1 INSTALLATION Disconnect by installer see Detail A 120V supply Refer to Table 16 2 for electrical requirements Drain line Normally closed fill valve by factory Makeup water supply piping by installer Open to drain Vent with check valve by installer 120V from unit disconnect or other source Normally closed fail closed min electric valve by installer Domestic water 80 psig max 1 25 m...

Page 23: ...d There are four knockouts on the right and left side of the enclosure It is recommended that electrical power is run into enclosure at these knockouts Outdoor Enclosure is designed for lifting by two methods Preferred method of lifting is by forklift This is only possible if the forks extend across entire unit Forks that do not extend across entire unit could cause tipping resulting in unsafe con...

Page 24: ... piping and drain piping in which case pipe chase cover should be removed Install insulation rated for 212 F 100 C to completely fill area around pipes to maintain proper enclosure pressure When enclosure is pad mounted or when pipe chase cannot be used supply water and drain piping can be run through the knockouts preferably on side opposite utility connections When ordered with heater package two...

Page 25: ... side is supplied with hardware Gasket must be installed between top of curb and base surface of Outdoor Enclosure to prevent moisture from leaking into building from driving rain or melting snow Installation drawing is included Four symmetrically shaped stand legs optional are include all necessary hardware for elevating Outdoor Enclosure 14 356 mm from ground Stand legs should be securely mounte...

Page 26: ...ating until it reaches a factory default tank temperature of 70 F 21 C This temperature can be field reset up to 180 F 82 C If temperature in enclosure is at or above 85 F 30 C but less than 150 F 66 C two ventilation fans turn on to cool the electronic components If temperature in enclosure is 150 F 66 C or higher a high limit switch powers down humidifier and the ventilation fans continue to run W...

Page 27: ...rain valve Fill valve Overflow port Install level Install level DN20 minimum condensate drain piping rated for 212 F 100 C Air vent height must be equal to or greater than dimension H2 see Table 23 1 Air vent tube Optional condensate return piping from dispersion unit Steam outlet Shock arrester recommended to reduce water hammer DN20 min drain skim and overflow piping rated for 212 F 100 C Manual o...

Page 28: ...20 minimum condensate drain piping rated for 212 F 100 C Air vent height must be equal to or greater than dimension H2 see Table 22 1 Air vent tube Steam outlet DN20 min drain overflow piping rated for 212 F 100 C DN20 drain valve If run is over 10 3 m increase pipe to 1 DN32 Flow line of drain piping after water seal must be below drain valve to ensure humidifier drains correctly 1 25 mm air gap Ov...

Page 29: ...into the building drain piping The Drane kooler option will temper 6 gpm 22 7 L m of 212 F 100 C water to 140 F 60 C To allow normal operation and prevent steam from escaping through the drain line the installer must provide a water seal of sufficient height to contain the pressure developed in the humidifier system See Table 23 1 for water seal heights Drain piping after the water seal must be pi...

Page 30: ...rflow fitting Prior to dumping into a drain the installer needs to connect the drain and overflow provide a water seal of height H1 from Table 23 1 and pipe Figure 25 2 provides fill and drain alternatives for Vaporstream humidifiers with the RO DI option Check valve Note Use a condensate pump rated for your application Pumps are rated by fluid temperature head pressure and flow gpm Contact your local Dr...

Page 31: ...e before connecting to ProBite connection Make sure drain line is clean round and free from damage 4 Mark insertion depth on drain line according to table below for your ProBite connection size 5 Push drain line into ProBite connection to insertion depth marked in Step 4 OM 7644 WARNING Do not insert fingers or any body part into ProBite connection openings Insert only piping into ProBite connecti...

Page 32: ... FILL NOISE IN TAP SOFTENED WATER HUMIDIFIER The primary component of the water supply assembly is the solenoid valve therefore noise can be expected during fill cycles If water hammer occurs when the fill solenoid closes the best solution is to install a shock arrester The noise might be diminished by reducing the supply water pressure minimum 25 psi 172 kPa or using flexible tubing rated for 212 F ...

Page 33: ...ous operating temperature DriSteem recommends installing 3 914 mm of non insulated stainless steel pipe directly off the humidifier between the humidifier and the nonmetallic tubing If using nonmetallic supply water tubing DriSteem recommends making a 2 50 mm water seal or loop in the supply line to isolate steam from the nonmetallic tubing See Figure 23 1 DriSteem recommends installing a strainer i...

Page 34: ...EC requirements and or governing codes For single stage units the fuse block and fuses are omitted in the control cabinet therefore the installer MUST provide a FUSED disconnect Multiple stage units require a service disconnect provided by the installer For European models locate the disconnect per IEC 60364 Refer to the detailed drawing of the disconnect location on Page 31 of this document Wirin...

Page 35: ...ontrol circuit side and the right side is the power circuit side Place conduit connection holes in the control cabinet so that the control and power wire routing is limited to their respective sides of the control cabinet Control wiring and power wiring must be run in dedicated or separated earthed metal conduit cable trays or trunking The control cabinet should be mounted in a location convenient...

Page 36: ...Note See tables on this page INSTALLATION Wiring Table 32 1 European wiring requirements 230 volt single phase 400 volt three phase Amps Wire size mm2 Ground wire size mm2 Amps Wire size mm2 Ground wire size mm2 0 18 2 5 2 5 0 15 7 2 5 2 5 18 1 24 4 4 15 8 21 4 4 24 1 30 7 6 6 21 1 27 6 6 30 8 42 7 10 10 27 1 37 5 10 10 42 8 57 16 16 37 6 51 16 16 57 1 75 7 25 16 51 1 66 7 25 16 75 8 93 7 35 16 66...

Page 37: ...commons A safety ground should never be used as a conductor or neutral to return circuit current When wiring external electrical connections to humidistats humidity and temperature transmitters or control signal input connections from a building control system use 18 gauge minimum 1 mm2 plenum rated twisted pair wire with cable shielding screening and drain wire for grounding Return all shielded s...

Page 38: ...ed within 10 3 m of the humidifier For wire lengths of 10 to 50 3 m to 15 m use 18 gauge 1 mm2 plenum rated shielded screened twisted pair wire with a bare drain wire for grounding GROUNDING REQUIREMENTS The approved earth ground must be made with solid metal to metal connections and must be a good conductor of radio frequency interference RFI to earth multistranded conductors Ground wire should be...

Page 39: ...lose to air grilles registers or heat radiation from room lighting C Acceptable Provides uniform mixture of dry and moist air If extended time lag exists between humidity generation and sensing extend sampling time D Acceptable behind wall or partition for sampling entire room if sensor is near an air exhaust return outlet Typical placement for sampling a critical area E Not acceptable These locat...

Page 40: ... distance was calculated during humidification system design and is dependent on several application parameters To determine your dispersion assembly s non wetting distance consult your system s design engineer or project documentation Non wetting distance can also be calculated using DriSteem s Dri calc sizing and selection software available at www dristeem com Note that your current design condi...

Page 41: ...g pitch requirements for single tube and multiple tube applications See Table 47 1 for interconnecting tubing pitch requirements for Rapid sorb applications Support interconnecting piping between the humidifier steam outlet and the dispersion system with pipe hangers Failure to properly support the entire steam piping weight may cause damage to the humidifier tank and void the warranty 90 elbows are...

Page 42: ...ulting in condensate discharge at the dispersion assembly Do not use steam hose for outdoor applications 2 Maximum recommended length for steam hose is 10 3 m Longer distances can cause kinking or low spots 3 5 80 5 450 204 80 24 4 5 100 5 750 340 100 30 5 5 125 5 1400 635 100 30 6 5 150 5 2300 1043 100 30 3 Insulate tubing to minimize loss of capacity and efficiency 4 Developed length of tubing eq...

Page 43: ...02 6 long 152 mm hose cuff Hose clamps Tubing Steam outlet connection tubing DC 1143 mc_022510_1600 Hose clamp Steam hose Steam outlet connection tubing DC 1142 Steam outlet connections Dispersion FIGURE 39 1 STEAM HOSE CONNECTION FIGURE 39 2 TUBING CONNECTION USING HOSE CUFF WITH CLAMPS ...

Page 44: ...s mc_022510_1603 DC 1141 Steam outlet connection flange Directional arm up down right and left by installer Swing arm by installer Support member Support tubing from above to prevent pressure on humidifier Allow for thermal expansion INSTALLATION Dispersion FIGURE 40 1 FLANGE CONNECTION ...

Page 45: ...rip tee by installer DriSteem part numbers for 304 stainless steel in line tees 1 diameter DN40 No 162710 2 diameter DN50 No 162712 1 25 mm air gap 8 200 mm minimum 6 150 mm minimum To dispersion assembly Insulate tubing and hard pipe to reduce steam loss 90 long sweep or two 45 elbows Obstruction Pitch INSTALLATION Drip tee installation Install a drip tee as shown in Figure 40 1 when Humidifier is...

Page 46: ...ain with a 1 25 mm vertical air gap Cut the drain line at a 45 angle on the end above the drain to permit a direct stream of water into the drain pipe while maintaining a 1 25 mm air gap Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam or condensing on nearby surfaces may occur All drain lines must be installed and sized according to governing codes mc_...

Page 47: ...ing for Single tube or multiple tube evaporative dispersion units Condensate drain Type of interconnecting piping Diameter of dispersion tube and interconnect ing piping Pitch of interconnecting piping Pitch of dispersion tube s Pitch of condensate drain Without drain Steam hose 1 DN40 2 ft 15 toward humidifier 2 ft 15 toward humidifier No drain 2 DN50 Tubing or pipe 1 DN40 1 8 ft 1 toward humidifier...

Page 48: ...efer to governing codes for drain pipe size and maximum discharge water temperature 2 Pitch steam hose or tubing toward humidifier 2 ft 15 when using steam hose ft 5 when using 1 tubing ft 2 when using 2 tubing 3 Dashed lines indicate provided by installer DC 1046a OM 351c Secure and seal escutcheon plates Table 44 1 Dispersion tube and condensate drain escutcheon plate dimensions for 1 tube for 2 ...

Page 49: ...ose or tubing Pitch pipe thread DN8 DC 1046b Secure and seal escutcheon plates Condensate drain tube by installer DN20 minimum Return line piping material must be suitable for 212 F 100 C water Note Condensate may be returned to the humidifier or wasted to a drain See Figure 43 1 for piping condensate to a drain Pitch steam hose or tubing toward humidifier 2 ft 15 when using steam hose ft 5 when usi...

Page 50: ...d humidifier 2 ft 15 when using steam hose ft 5 when using 1 tubing ft 2 when using 2 tubing Secure and seal escutcheon plates Open drain required Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam otherwise condensation may form on nearby surfaces Refer to governing codes for drain pipe size and maximum discharge water temperature Multiple dispersion tube...

Page 51: ...mber A single duct escutcheon plate the size of the header Slip couplings or hose cuffs and clamps Accessories such as duct plates slip couplings or hose cuffs Bolts and washers for mounting the dispersion tubes to the bracket L bracket mounting holes see note at left L bracket 50 1270 mm long or shorter has a mounting hole 4 102 mm from each end for mounting the L bracket to the duct or air handl...

Page 52: ...cient length to accommodate the 1 8 ft 1 pitch requirements toward the pipe thread DN20 header drain fitting 2 DN50 dispersion tubes The bracket can be mounted flush to the ductwork The 1 8 ft 1 pitch typically can be accomplished in the length of the hose cuffs used to connect the tubes to the header See the table below and the drawings on the following pages for pitch requirements mc_060210_0953 N...

Page 53: ... dispersion tubes Use the L bracket as a template to mark the holes on the duct floor 2 Temporarily loosely suspend or support the header below the final location Vertical balance point of the dispersion tube length dictates where the header should be suspended or temporarily supported 3 Mount the dispersion tubes to the header with the slip coupling or hose cuff provided When installing slip coup...

Page 54: ... header stub for O rings to provide a seal High end of L bracket can be fastened tight to duct or air handler Fastener on low end of L bracket must be long enough to compensate for pitch Use a nut on both sides of L bracket and duct or air handler for stability For 2 DN50 dispersion tubes Fasten bracket to top of duct and use hose cuffs to compensate for header pitch Before securing hose cuffs wit...

Page 55: ... ft 1 Secure and seal escutcheon plate Pitch Pitch steam hose or tubing toward Rapid sorb 2 ft 15 when using steam hose 1 8 ft 1 when using tubing Stainless steel support Rapid sorb HEADER INSIDE OF DUCT HORIZONTAL AIRFLOW 1 Mark and cut holes in ductwork or air handler for steam header penetration condensate drain piping and header support bracket fastener Allow 1 8 ft 1 header pitch toward the s...

Page 56: ...d bolt lock washer and flat washer 8 Rotate the assembly up until the L bracket aligns with the mounting holes in the duct or air handler For 1 DN40 dispersion tubes Header pitch is duplicated in the L bracket Dispersion tube and slip coupling must be fully engaged on header stub for O rings to provide a seal High end of L bracket can be fastened tight to duct or air handler Fastener on low end of...

Page 57: ...ONNECTIONS TO RAPID SORB HEADER Piping must be minimum I D DN20 and rated for 212 F 100 C minimum continuous operating temperature The condensate drain line must be piped as shown in Figures 48 1 and 50 1 Provide a 6 152 mm drop prior to a 5 127 mm water seal to Ensure drainage of condensate from the header Keep steam from blowing out of the drain line After the water seal run the drain line to an...

Page 58: ...coach screw For hollow block or poured concrete wall mounting position template in place and mark the holes Drill appropriate pilot hole for two 3 8 M10 toggle bolts or two 3 8 M10 machine bolt lead anchors expansion bolts Secure SDU frame in place To provide power to the SDU run a neutral line with 208V 240V single phase and 208V three phase power supply lines to provide a 120V circuit for the fa...

Page 59: ...t Front view Side view 16 1 409 mm Steam inlet 2 25 57 mm DC 1078 DN20 pipe thread drain nipple See Note below 3 2 82 mm Note SDU E requires a condensate drain line and water seal provided by installer See Figure 55 1 Table 55 1 SDU specifications SDU model Maximum capacity Shipping weight Amps at 120V 50 60 Hz Horse power cfm m3 s dB lbs hr kg h lbs kg SDU I 30 13 6 68 31 3 20 1 5 760 0 36 58 SDU...

Page 60: ...ed and sized according to governing codes 5 The drain line should have a union installed directly on the dispersion box nipple to accommodate future removal of the SDU E shroud 6 A drain line and water seal must be connected to the SDU E fan unit dispersion box nipple If the condensate is not drained from the dispersion box standing water will accumulate See Warning below 7 The dispersion box is c...

Page 61: ...inimum nonwetting dimensions in this table Rise The minimum nonwetting height above the steam outlet of the SDU E Spread The minimum nonwetting width from the steam outlet of the SDU E Throw The minimum nonwetting horizontal distance from the steam outlet of the SDU E mc_042710_1300 SDU E SDU E RISE SPREAD AND THROW As steam is discharged from the SDU E it quickly cools and turns to a visible fog ...

Page 62: ...e until becoming absorbed The Area type fan and brackets are shipped separately and field installed on the humidifier After mounting the fan terminate the wires as specified on the wiring diagram To provide power to the Area type fan run a neutral line with 208V 240V single phase and 208V three phase power supply lines to provide a 120V circuit for the fan With all other power supply voltages other t...

Page 63: ...Rise Spread Throw lbs hr kg h ft m ft m ft m ft m ft m ft m ft m ft m ft m 50 20 1 0 0 3 1 5 0 5 4 0 1 2 1 0 0 3 2 0 0 6 4 0 1 2 1 0 0 3 2 0 0 6 4 0 1 2 75 34 2 0 0 6 2 0 0 6 6 0 1 8 2 0 0 6 2 5 0 8 6 0 1 8 2 0 0 6 2 5 0 8 6 0 1 8 100 45 3 0 0 9 3 0 0 9 8 0 2 4 3 0 0 9 3 0 0 9 8 0 2 4 3 0 0 9 3 0 0 9 8 0 2 4 150 68 4 0 1 2 4 0 1 2 10 0 3 1 4 0 1 2 4 0 1 2 11 0 3 4 4 0 1 2 4 0 1 2 11 0 3 4 200 90 5...

Page 64: ...r units water skims from the humidifier after every fill cycle Adjust the amount of skim by increasing or decreasing the skim time see the Vapor logic Installation and Operation Manual 10 At start up DriSteem recommends initially running the humidifier with the factory default setting for skim time See Maintenance beginning on Page 61 mc_060210_1400 VLC The Vapor logic Installation and Operation M...

Page 65: ...valve is closed Turn on power to the humidifier and confirm the Main menu is displayed on the keypad display The display may take several seconds to appear as the controller powers up Confirm in the Main Menu that the mode is Auto and that tank status is Filling When Filling appears in main menu confirm that the tank is filling with water In the Status screen confirm that the Duct Airflow Switch is close...

Page 66: ...nd inspect it for mineral deposits after three months of duty Hours of operation and duty cycle will determine your maintenance schedule as will water quality Water quality Maintenance requirements vary with water quality because tap and softened water carry a variety of minerals and other materials in a mix that varies from location to location Very hard high mineral content water requires more f...

Page 67: ...s Insulated and uninsulated tanks will have hot surfaces Verify that there is no call for humidity and that the aquastat set point adjusted using the keypad display Setup screens is less than room temperature default setting is 40 F 4 C so that the heaters do not energize while cooling down the tank Models with a standard drain valve Manually open the drain valve by moving the valve lever located ...

Page 68: ...sembly through the probe cover located on the end of the heater terminal cover Disconnect the probe plug and cable assembly and unscrew the probe rod assembly from the humidifier probe housing using the probe tool see Figure 64 1 Inspect the probe housing and clean ensuring that all the housing passageways for water flow are clear Remove the housing from the holding bracket by removing the humidifier...

Page 69: ...ulation Remove the water seal piping from the humidifier and flush out Replace the water seal with new piping if the minerals have hardened in the water seal Install a union at the base of the water seal to ease removal if water quality causes the water seal to become clogged often with scale When the maintenance requirements are complete Slide the cleanout tray back into the tank Hook the tab on th...

Page 70: ...ile cooling down the tank For models with a standard drain valve Manually open the drain valve The float valve opens Let the fill water run until the tank is cooled then shut off the field installed manual supply water shut off valve Let the tank drain then manually close the drain valve For models with end of season drain option Use the keypad display to perform the cool down process Select Manual D...

Page 71: ...ree water is used in the RO DI water Vaporstream no cleaning or flushing of the humidifier should be necessary 2 Off season maintenance Perform a complete inspection of the following Heaters Float valve Low water cutoff switch Humidifier tank and gaskets After inspection the humidifier should remain empty until humidification is required Inspection and maintenance Recommendations for RO DI water humidi...

Page 72: ...g service or maintenance procedures on an part of the humidification system When performing maintenance on the humidifier Always switch the keypad control mode to Standby Place all power disconnects in OFF position and lock in OFF position Close the field installed manual supply water shut off valve mc_031110_0444 Table 68 1 Outdoor Enclosure troubleshooting guide Symptom Possible cause Recommended a...

Page 73: ...TION OPERATION AND MAINTENANCE MANUAL Note Components may be in a different location or have a different orientation than shown in drawing Humidifier REPLACEMENT PARTS FIGURE 69 1 VAPORSTREAM TANK REPLACEMENT PARTS VLC OM 033 ...

Page 74: ...Float valve assembly Vaporstream with RO DI water 14 Temperature sensor All 405760 002 15 DIN rail mounted terminals All 16 Probe plug assembly Vaporstream with tap softened water 406050 101 17 Probe assembly Vaporstream with tap softened water 406303 111 18 Low water tube Vaporstream with RO DI water 167790 19 Low water cut out switch Vaporstream with RO DI water 408420 002 20 Gasket probe All 30...

Page 75: ...onents may be in a different location or have a different orientation than shown in drawing FIGURE 71 1 NORTH AMERICAN CONTROL CABINET REPLACEMENT PARTS FIGURE 71 2 EUROPEAN CONTROL CABINET REPLACEMENT PARTS Note Components may be in a different location or have a different orientation than shown in drawing OM 7659b ...

Page 76: ...sket SSR SSR control 20 Cover SSR SSR control 165545 22 Board Vapor logic keypad display All 408495 002 23 Wire data cable 27 Mounted keypad display 408490 014 24 Cable assembly Vapor logic keypad display All 408490 Specify humidifier model and serial number when ordering Control cabinet REPLACEMENT PARTS Table 72 2 European control cabinet replacement parts No Description Part no 1 Main controller...

Page 77: ...o Description Qty Part number 1 Shroud 1 330001 002 2 Blower SDU external assembly 1 3 Switch airflow 1 406190 4 Screw 8 32 Phillips black 6 700170 007 5 Nut retainer 8 32 6 409593 001 6 Tubelet 0 375 0 375 molded 44 310280 006 This is an assembly of multiple parts mc_062810_1113 mc_062810_1111 FIGURE 73 1 SDU I REPLACEMENT PARTS ...

Page 78: ...hroud 1 330002 001 2 Blower SDU external assembly 1 3 Switch airflow 1 406190 4 Screw 8 32 Phillips black 4 700170 007 5 Nut retainer 8 32 4 409593 001 6 Dispersion chamber for SDU with 1 outlet 1 160445 003 Dispersion chamber for SDU with 2 outlet 1 160445 004 This is an assembly of multiple parts mc_062810_1112 mc_062810_1110 FIGURE 74 1 SDU E REPLACEMENT PARTS ...

Page 79: ...umber in drawing Description Part number 1 500W strip heater 405800 052 2 1100W strip heater 405800 053 3 Cooling fan 405800 068 4 Gasket door or roof 308005 010 5 Stat high limit 405800 065 6 Stat low limit 405800 066 7 Stat heater 405800 066 8 Stat fan 405800 067 Specify quantity in feet FIGURE 75 1 OUTDOOR ENCLOSURE REPLACEMENT PARTS 5 2 4 3 4 1 6 7 ...

Page 80: ...gal theory even if DriSteem has notice of the possibility of such damages By purchasing DriSteem s products the purchaser agrees to the terms and conditions of this Limited Warranty Extended warranty The original user may extend the term of the DriSteem Limited Warranty for a limited number of months past the initial applicable warranty period and term provided in the first paragraph of this Limite...

Reviews: