VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
When selecting a location for the humidifi er, consider the following:
• Easy access for maintenance
• Maximum ambient temperature for the control cabinet is 104 °F (40 °C).
• Noises inherent to operation:
– Fill cycles (tap/softened water humidifi er)
See
Fill noise in tap/softened water humidifi er
on Page 28.
– Control cabinet: cycling contactors
• Clearance recommendations — primarily top, left side, and front (see
Figure 9-1).
• Convenient location to dispersion system for routing of steam hose or tubing
(see
Dispersion
section of this manual).
• Electrical connections: Power, control, and safety circuits
• Plumbing connections: Supply water, drain piping, and condensate return
piping (see the
Piping
section of this manual)
• Water seal requirements (see
Piping
section of this manual)
• Avoid locations above critical equipment or processes.
• Avoid locations close to sources of electromagnetic emissions, such as
power distribution transformers and high horsepower motors controlled by
variable frequency drives.
Selecting a location
Top:
18" (457 mm)
Right side
6" (152 mm)
Floor:
24" (610 mm)*
Front:
36" (914 mm)
Cleanout
plate
Back:
6" (152 mm)*
Left side:
36" (914 mm)*
Cleanout tray
*
When the control cabinet is mounted on the Vaporstream, provide 36" (914 mm) clearance from the front of the control cabinet and 6" (152 mm)
from the bottom of the cabinet to the fl oor.
See Dispersion, beginning on page 35, for
dispersion assembly placement guidelines.
Important:
Installation must comply with governing codes.
Top:
18" (457 mm)
Right side
6" (152 mm)
Floor:
24" (610 mm)*
Front:
36" (914 mm)
Cleanout plate
Back:
6" (152 mm)*
Left side:
36" (914 mm)*
DC-1181
OM-7637
FIGURE 9-1: VAPORSTREAM CLEARANCE RECOMMENDATIONS