VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Table 38-1:
Maximum steam carrying capacity and length of interconnecting steam hose or tubing
Steam hose
1
Copper or stainless steel tubing
Hose I.D.
Maximum capacity
Maximum length
2
Tubing size
Maximum capacity
3
Maximum developed
length
4
inches
DN
lbs/hr
kg/h
ft
m
inches
DN
lbs/hr
kg/h
ft
m
1½
40
150
68
10
3
1½
40
150
68
20
6
2
50
250
113
10
3
2
50
220
100
30
9
1. When using steam hose, use DriSteem steam hose for best results.
Field-supplied hose may have shorter life and may cause foaming
in the evaporating chamber resulting in condensate discharge
at the dispersion assembly. Do not use steam hose for outdoor
applications.
2. Maximum recommended length for steam hose is 10' (3 m). Longer
distances can cause kinking or low spots.
3
5
80
5
450
204
80
24
4
5
100
5
750
340
100
30
5
5
125
5
1400
635
100
30
6
5
150
5
2300
1043
100
30
3. Insulate tubing to minimize loss of capacity and effi ciency.
4. Developed length of tubing equals measured length plus 50% of measured
length, to account for fi ttings.
Longer tubing lengths are possible at capacities lower than listed
maximums. Consult factory.
5. Requires fl ange connection.
Note: Capacities and lengths in this table are based on total maximum pressure drop in hose or tubing of 5" wc (1250 Pa).
mc_091410_1050-VLC
Interconnecting piping requirements
INSTALLATION