10
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
To ensure that the water level control system works properly, the tank must be
mount ed level from side to side and front to back.
The mounting methods described in this manual are the only options available
to maintain compliance to the UL 998 standard; alternate mounting methods
will compromise the humidifi er’s CE, ETL, and C-ETL approvals.
Table 10-1:
Mounting options by model
Mounting method
Models
2-1, 3-1, 4-1, 5-1
All other models
Standard
Optional
Standard
Optional
Trapeze
X
X
Support legs
X
Wall brackets
X
X
Weather cover
X
X
Outdoor Enclosure
X
X
mc_022310_1354
VLC-OM-006
Optional set of four
legs and hardware
INSTALLATION
Mounting:
SUPPORT LEGS
Support legs are not available for single-heater models (2-1, 3-1, 4-1, and
5-1). These models must be mounted with a trapeze (Page 11) or an
Outdoor Enclosure (Pages 14 through 21).
Use enclosed bolts, nuts, and washers to fasten legs to tank. Shim or adjust so
the tank sets level side to side and front to back. Verify level after the tank is
fi lled and is at operating weight.
WARNING
Mounting hazard
Mount humidifi er per the instructions
in this manual and to a structurally
stable surface. Improper mounting of
the humidifi er can cause it to fall or tip,
resulting in severe personal injury or
death.
mc_060110_1540
FIGURE 10-1: SUPPORT LEGS
Overview