15
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Outdoor Enclosure:
INSTALLATION
Notes:
1. The Outdoor Enclosure has two available steam
dis tri bu tion confi gurations:
The standard con fi g u ra tion has a steam outlet
at the back of the Outdoor Enclosure for
con nect ing to steam dispersion unit piping.
The optional internal steam dis tri bu tion
con fi g u ra tion routes steam within the Outdoor
Enclosure and down through the enclosure pipe
chase into a building.
2. There are four knockouts located on the right
and left side of the enclosure. Knockout sizes
are 1½" (hole dia. 50 mm) for Vaporstream
models with 1-6 heaters and 2" (hole dia. 63.5
mm) for Vaporstream models with 9-12 heaters.
Run the electrical power into the en clo sure at
these knockouts.
3. All piping from the Vaporstream unit to the
steam outlet is stainless steel pipe. Depending
on the application, interconnecting piping from
the steam outlet to the dispersion assembly can
be tubing or DriSteem steam hose. See the
Dispersion section of this document for more
information about connecting to the dispersion
assembly.
4. A separate 20 amp, 120 Vac service must be
brought to the Outdoor Enclosure to power the
enclosure heaters and fans.
DC-1481
Optional
steam
outlet
Ventilation fan
Knockouts, 4"
(102 mm) on center
Enclosure drain 1½"
pipe thread (DN40)
with male nipple
Pipe chase
G
A
Vaporstream humidifi er
Standard
steam
outlet
See Note 2
Ventilation fan
K
4.5"
L
mc_030410_1500
FIGURE 15-1: VAPORSTREAM OUTDOOR ENCLOSURE WITH STANDARD OR OPTIONAL STEAM OUTLET, ELEVATION VIEW
Overview