55
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Control board
in Vaporstream
control cabinet
VLC-OM-032
SDU-I cabinet with
shroud removed
SDU-I and SDU-E
Control board
in Vaporstream
control cabinet
VLC-OM-024
SDU-E cabinet with
shroud removed
Humidifi ed air
discharge grille
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40) steam inlet
Front view
Side view
16.1"
(409 mm)
Air intake grille
2.25" (57 mm)
DC-1076
Steam outlet
24.2"
(615 mm)
18.6"
(472 mm)
10.9"
(276 mm)
1½" (DN40)
or 2" (DN50)
steam inlet
Front view
Side view
16.1"
(409 mm)
Steam inlet
2.25"
(57 mm)
DC-1078
¾" (DN20) pipe
thread drain
nipple. See
Note below.
3.2" (82 mm)
Note: SDU-E requires a condensate drain line and water seal, provided by installer. See Figure 55-1.
Table 55-1:
SDU specifications
SDU
model
Maximum capacity
Shipping weight
Amps at
120V
(50/60 Hz)
Horse
power
cfm
m
3
/s
dB*
lbs/hr
kg/h
lbs
kg
SDU-I
30
13.6
68
31
3.20
1/5
760
0.36
58
SDU-E
102
46.3
61
28
2.07
1/8
545
0.26
64
* Measurement taken 6.5' (2 m) in front of SDU cabinet.
mc_042710_1440
mc_052510_1700
mc_052510_1701
INSTALLATION
Dispersion:
FIGURE 55-1: SDU-I MECHANICAL DETAIL
FIGURE 55-3: SDU-E MECHANICAL DETAIL
FIGURE 55-2: SDU-I FIELD WIRING
FIGURE 55-4: SDU-E FIELD WIRING