3
VAPORSTREAM INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Product overview
OM-1000
Cover
fastener
Cover
Float valve
Overfl ow
Low-water
cutoff
Drain valve
Humidifi ers using tap or softened water control
water levels electronically using a three-rod
probe. The controller responds with the above
actions when the water level reaches each rod.
VLC-OM-030
Supply water connection
Float rod
See Pages 22 and 23 for detailed installation
drawings.
Damage caused by chloride corrosion is not
covered by your DriSteem warranty.
Humidifi ers using RO/DI water control water
levels using a fl oat valve and low-water cutoff
switch.
Float ball
VLC-OM-026
Fill valve opens when
water level is below this
probe.
Low-water cutoff. Power
to heaters is cut if water
level drops below this
probe.
Fill valve closes when
water level rises to this
probe.
mc_030910_1335
mc_030910_1336
WATER TYPE CONVERSION
Vaporstream tap/softened water humidifi ers can be converted in the fi eld
for use with RO/DI water, and Vaporstream RO/DI water humidifi ers can be
converted in the fi eld for use with tap/softened water. Contact your DriSteem
representative or distributor for parts and instructions.
mc_061610_1640-VLC
OVERVIEW
FIGURE 3-1: VAPORSTREAM HUMIDIFIER, RO/DI WATER OPTION
FIGURE 3-2: WATER LEVEL CONTROL
FOR TAP/SOFTENED WATER HUMIDIFIER
FIGURE 3-3: WATER LEVEL CONTROL
FOR RO/DI WATER OPTION HUMIDIFIER