Magnet
Axis
with
Valve Closed
Clockwise to Close
Clockwise to Open
45
°
Check Out, Configuration and Calibration
Check Out Procedures
19
Figure 10
Magnet Orientation for 90 Degree Valve Rotation with Valve Closed
Table 4 Reciprocating Valve Mounting Hole Selection
Actuator Size
Stroke
Mounting Hole
Lever Hole
Turnbuckle
Length
6 and 10
0.5 - 0.8 inch
A
A
1.25 inch
10
0.5 - 0.8 inch
A
A
1.25 inch
10
>0.8 – 1.5 inch
B
B
1.25 inch
16
0.5 - 0.8 inch
B
A
2.90 inch
16
>0.8 – 1.5 inch
C
B
2.90 inch
16
>1.5 – 2.5 inch
D
C
2.90 inch
23
0.5 - 0.8 inch
B
A
5.25 inch
23
>0.8 – 1.5 inch
C
B
5.25 inch
23
>1.5 – 2.5 inch
D
C
5.25 inch
Using ValVue 2.4 to Check Magnet Position
Use this procedure to check the magnet using ValVue 2.4 or greater.
1.
Connect to the positioner in accordance with the ValVue
2.4 instructions. (For further information refer to the
ValVue 2.4 Instruction Manual, EW1003.)
After the positioner has been installed and set up
with a HART Modem in a HART compliant
communications loop, install ValVue 2.4 on the
computer that is connected to the HART modem.