Check Out, Configuration and Calibration
Configuration
25
System Requirements
ValVue Lite runs on IBM compatible computers. Minimum requirements
for all versions of ValVue software are Windows 2000, and XP, 16 MB
RAM, a serial or USB port connected to a HART modem, and a
CD-ROM drive.
ValVue 2.4 Full Trial Version
The SVI II AP comes with a copy of ValVue Trial Version software that
can be used for sixty days without a license. After the 60-day trial
period, ValVue 2.4 must be registered. ValVue 2.4, full version,
provides advanced diagnostic, maintenance capabilities and basic
calibration and configuration for the SVI II AP. SVI II AP performs valve
diagnostics and displays stroking speed, step response, cumulative
travel, cycles, and operation in near-closed position. The software
stores test results for comparison with future results for predictive
maintenance. Password protected access to remote instruments is set
up with administration features. The fully licensed ValVue 2.4 software
is available as an upgrade.
Pushbuttons and Local Display
This section covers the optional local interface consisting of the LCD
alphanumeric display and pushbuttons. Operation of the SVI II AP
Positioner as a local device is controlled through the optional device-
mounted pushbuttons and digital display, shown in Figure 12 on page
26. Using the display you can read the input signal, valve position, and
actuator pressure. The display sequences from one variable to the next
every 1.5 seconds.
Using the pushbuttons you can exit from operating mode at any time
and step through a menu structure to perform a wide range of manual
operation, calibration, configuration, and monitoring functions that are
described later in this section. ValVue 2.4 is used to perform all
diagnostics functions. The pushbuttons do not support diagnostics
functions.
The SVI II AP has two operational modes: Normal Operating Mode and
Manual Mode and two setup modes, Configuration and Calibration.
The SVI II AP also has two modes for handling of faults and power-up:
Reset and Failsafe. When commissioning or checking a control valve
with SVI II AP fully installed the following steps are recommended:
Change mode to Manual mode
Examine and adjust all CONFIGuration items
Enter Calibration mode
Run STOPS to automatically calibrate stroke
Run autoTUNE to set dynamic response
Examine the device STATUS
Introduce manual set point changes to verify
dynamic performance