Masoneilan Dresser
SVI II AP Quick Start Guide
28
VIEW DATA Settings
Table 7 VIEWDATA Settings
Typical Setting
Optional Setting
SINGLE
DOUBLE
ATO
ATC
LINEAR
EQUAL 30 EQUAL 50 QUICK 50 CUSTOM CAMFXEQ
PSI
BAR
KPA
0.00
TS OFF
2.00
TS ON
4.00
SIG LO
4.00
SIG LO
20.00
SIG HI
12.00
SIG HI
English
French
Calibration
Pilot Trim Valve Applications require the use of the Manual Stop
calibration procedure (refer to “Configuration and Calibration” of the
SVI II AP Instruction Manual, EW2002-AP). Do not run “Find Stops” or
the ValVue “Setup Wizard” on valves with Pilot Trim or damage to the
valve will occur.
To calibrate the SVI II AP:
1.
Observe the display following power-up. The SVI II AP will
power up in the previously active mode either MANUAL or
NORMAL (operating) mode.
2.
If in NORMAL mode, the display will alternate between
POS and SIGNAL indicating Normal mode.
3.
If in MANUAL, the display will alternate between POS –M
and SIG indicating MANUAL mode.
4.
With MANUAL mode displayed, press * to select the
MANUAL mode.
5.
Press + again;
↓
CONFIG appears. Pr again
brings
↓
CALIB.
6.
Select CALIB by pressing *. STOPS appears. The valve
moves full open and back to full closed. Observe all
warnings.
7.
Press * to cause the valve to stroke and to automatically
calibrate valve travel.
10.
After the STOPS procedure finishes, press + twice until
TUNE appears.