Masoneilan Dresser
SVI II AP Quick Start Guide
22
Making Connections to the Terminal Board
Each terminal block on the terminal board has a cage clamp connector.
One side of the connector has the actual connection for the wire, with
a lever at the top. If there is an option present that is not properly
connected to the terminal board or if adding a new option, connect the
wires from the option as follows:
1.
If the option’s wires have not been stripped, strip the
insulation at the end of wires.
2.
Locate the correct terminal block on the terminal board
(see Figure 11 on page 21).
3.
Push the lever back at the top connector until you see the
opening for wire insertion. (The connectors are spring
activated and may require a lot of pressure to move the
lever.)
4.
Insert the wire into the opening and release the lever.
Operational
Checkout
The operational checkout of the SVI II AP consists of:
Connecting the SVI II AP to a current source
Checking the pushbutton locks
Powering up the SVI II AP
Connecting to the Current Source
Connect to a DC mA current source then check and configure with the
local display and pushbuttons, if so equipped. The following section
describes configuration and calibration with the optional local display
and pushbuttons. If the SVI II AP is not equipped with local display use
ValVue Lite and a PC with a HART modem or a HART Handheld
Communicator.
Note:
When an SVI II AP is turned on it is advisable to apply the air
supply before applying the electrical input signal.