17
2
Check Out, Configuration
and Calibration
Overview
This section provides the calibration procedures to ensure proper valve
positioning. Operational checkout, configuration and calibration
procedures are described using an SVI II AP that has a display with
pushbuttons.
Note:
You should perform all procedures in this section before putting
the SVI II AP into operation.
Check Out
Procedures
SVI II APcheckout consists of physical and operational checkout
procedures. The physical checkout procedures are listed below:
Inspect the Actuator, Linkages, or Rotary Adapter
Verify the Mounting and Linkage Adjustment
Check the Magnet
Check the Air Supply
Check the Electronic Module Connections
Physical Inspection
You should inspect the following components of the SVI II AP:
Valve Mounting
The Air Supply
Actuator, Linkages, or Rotary Adapter
Verify that the mounting has not been damaged in shipment for a pre-
mounted SVI II AP, physically inspect the actuator, linkage. Record the
following information for the configuration checkout:
1.
Valve Air to Open (ATO) or
2.
Air to Close (ATC)
3.
Actuator pressure rating
4.
Actuator bench range
5.
Inherent trim characteristic of the control valve; linear,
equal percentage, or other.
Note:
Refer to the valve data sheet or model number of control valve.