Masoneilan Dresser
SVI II AP Quick Start Guide
16
2.
Using the 3mm hex key, remove the screw from the lower
left corner, connecting the terminal board to the SVI II AP
housing.
3.
Connect the cable from the display into the LCD connector
on the terminal board.
4.
Ensure that the gasket is in its groove in the housing.
5.
Place the cover over the screw mounts.
6.
Tighten the four screws with the 5 mm hex key.
7.
After installing the new display you will have to power up
the unit (refer to “Powering Up the SVI II AP” on page 23 of
this guide for further information).
Note:
The cover of the SVI II AP is a critical component for safety in
Hazardous Areas. To ensure safe operation the flat surfaces of
the cover and the housing must be clean and absolutely free of
particles or dents. There must be no gap between the housing
and cover; torque spec is 50 in/lb.
Make sure that:
1.
The gasket is seated in the groove in the housing flange.
2.
No wires or retaining cable can be trapped under the cover
flange.
3.
The flange area is not corroded and the surface is not
scarred.
4.
The four cover bolts are securely tightened to 50 in/lb.