54
12.10.2Advanced Configuration
To access the
Details
configuration screen, click the
Details>>
on the right of the
Description
cell.
Fig.12.10.2.1
The Advanced Provisioning > Analogs menu
From the
Details
configuration screen, you can now select which temperature units you want to use, define
alarm "set" and "clear" descriptions, and define Qualification settings.
Aanalogs (Details>>)
Record Freq
The amount of time, in minutes(min) or seconds (s), between each log of
each analog value to history.
Deadband
The amount (in volts) that the channel needs to go above or below a
threshold in order to cause an alarm.
On set
User-definable description (condition) that will appear for the temperature
alarm on Set. Example: "Alarm"
On clear
User-definable description (condition) that will appear for the temperature
alarm Clear. Example: "Clear"
Qual. Time
(Qualification Time)
The length of time that must pass, without interruption, in order for the
condition to be considered an Alarm or a Clear.
Qual. Type
(Qualification Type)
Allows you to choose whether you want to apply the Qualification Time to
the alarm Set, Clear, or Both.
Units
User-definable display units or optional choice between Fahrenheit and
Celsius temperatures. The most common are:
VDC = Voltage
%H = Humidity
F = Fahrenheit
C = Celsius
Low ref
User-definable lower threshold settings
High ref
User-definable upper threshold settings
Thresholds
These settings are set to indicate the severity of the alarm depending on
which threshold values have been passed. Enter values for Major Under
(MjU0, Minor Under (MnU), Minor Over (MnO) and Major Over (MjO).
*
These values are gathered from your sensor. Keep in mind that the NetGuardian is trying to build a