Spaces included here are for readability purposes only.
!
Hot Tip!
·
Precedence of the operations are always left to right.
·
All number references can either be one or two digits.
_OR D1.3-5
is logically equivalent to (1.3 || 1.4 || 1.5)
_AN D 1.3-5 D2.6 _OR D3.7
is logically equivalent to ((1.3 && 1.4 && 1.5 && 2.6) || 3.7)
_OR D01.03-05 D02.06 _AN D02.07 D03.10.-12
is logically equivalent to ((1.3 || 1.4 || 1.5 ||
2.6&&(2.7 && 3.10 && 3.12))
_AN D1.3-5D2.6_OR.7D3.10.12
is logically equivalent to ((1.3 && 1.4 && 1.5 && 2.6 ) || 2.7 ||
3.10 ||3.12))
Controls
12.9
The NetGuardian LT G2's relay can be configured in the
Provisioning
>
Controls
menu. You can enter your
own description for this relay and assign notification device(s).
Fig. 12.9.1
The Provisioning > Controls menu
Controls
Description
User-definable description for the NetGuardian LT G2's control.
Derived Description
Control relays and virtual alarms can be created with a derived formula and tested
with the Parse button. See below for more information.
Mom. Time
Control on time (in milli-seconds) when you execute the MOM command. Max
limit of 600 seconds.
Notification Devices
Check which notification device(s), 1 through 8, you want to send alarm
notifications for the control.
Derived controls can be created from derived formulas using the following operations:
_OR
: Set the current operation to OR.
_AN
: Set the current operation to AND.
_XR
: Set the current operation to XOR.