Setting Up Simultaneous Doors
The purpose of the this setup is to synchronize two
side-by-side doors for simultaneous operation.
Connecting the Controllers
Header
Presence
Swing
Presence
Approach
Presence
Safety
Beam
+24V
TRIGGER
COM
+24V
HEADER
DATA
COM
+24V
SWING
COM
+24V
APPR.
COM
+24V
BEAM
COM
C
O
N
T
R
O
L
L
E
R
1
Header
Presence
Swing
Presence
Approach
Presence
Safety
Beam
+24V
TRIGGER
COM
+24V
HEADER
DATA
COM
+24V
SWING
COM
+24V
BEAM
COM
C
O
N
T
R
O
L
L
E
R
2
OFF
GND
H.O.
Mode
Switch
OFF
GND
H.O.
RXD
TXD
GND
RXD
TXD
GND
GND
FIRE
GND
.
.
+24V
APPR.
COM
Fire
sensor
•
Connect the grounds of the two controllers together.
•
Connect the knowing act activation device to both
controllers in parallel.
•
Connect the presence sensor to both controllers in
parallel, except for the Data Line.
•
Let each controller power it’s presence sensors
•
Connect a single program switch to both doors in
parallel.
•
Connect the RXD line of each controller to the TXD
line of the other controller.
•
If you use the “Fire” input, connect the Fire sensor
to both controllers.
•
If you use the “Breatout” input, connect the Breakout
switch to both controllers.
•
Connect both controllers to the same AC power source.
•
Program the two controllers identically
(Continued on following page)