DOLD SAFEMASTER S LH 5946 Operating Instructions Manual Download Page 11

11

LH 5946 / 130910 / 363

Failure indication with flash code of LED „ERR“

The flash codes indicate failures caused externally (see diagram flashing 
codes for failure indication on page 9).
A series of flash pulses 1-5 followed by a slightly longer space is displayed. 
The flash code indicates the type of failure. If several failures are present at 
the same time only the failure with the highest priority (lowest flash code) is 
shown. When this failure is removed the other existing failures are displayed 
in the same way according to their priority.

Failure storing / reset (terminals X2-X3)

With the external failures broken wire/offset and feedback circuit the operator 
can choose between manual and automatic reset after the failure is removed.
X2-X3 open: 

 

manual reset

X2-X3 closed: 

 

automatic reset

 

Attention

The a.m. storing function of the external failures broken wire /offset, 
and feedback circuit is not a safety function. I.e. in respect to safety 
aspects it can not be regarded as guaranteed. The reset for these failures 
must be therefore regarded as auto reset after removing the faults.

Internal device failures that could occur in seldom cases  (e.g. caused 
by temporary interference) can be reset by switching the supply volta-
ge off and on. If a reset is not possible also if the voltage is applied 
correctly, the device could be defective and should be sent back to 
the manufacturer for examination or repair.

 Function

The LH 5946 has to be connected according to connection examples or in 
a similar way. The connection of DC- motors is made as with single phase 
AC-motors.

L1 - L2 - L3

The measuring wires L1-L2-L3 have to be connected directly to the win-
dings of the monitored motor (not via transformers) in order to provide a 
correct broken wire detection for the connection wires and motor windings.
The motor windings must not be disconnected from the measuring wires by 
motor contactors, because broken wire detection is activated and standstill 
monitoring is disabled.
 
Interference to the measuring wires should be avoided as no standstill may 
be detected by the LH 5946. If possible the measuring wires should be run 
separately from the motor wires or screened wires should be used. In this 
case the screen can be connected at the motor side.

A1 - A2

Connection of the auxiliary supply, recommended fuse : 2A.

A3+ / A4

DC 24 V supply (12 … 30 V) for the semiconductor monitoring outputs „ON“ 
and „ERR“, if these are used.

11-12, 23-24, 33-34, 43-44

Safety output contacts, connection according to the connection examples 
or similar.
Recommended fuse: 5 A fast acting, to avoid welding of  the contacts in 
the case of external wiring or component failures. See also technical data.

  Connection of LH 5946

  Connection of LH 5946

53 - 54

Monitoring contact to indicate the state of the safety output (non safety contact)

X1 - X2 (feedback circuit)

Connection of NC contacts of external components or contactors for contact 
re-enforcement, must be linked if not used.

X2 - X3

Connection for manual or auto reset, connection is made according to the 
required application. When monitoring DC motors or in the case of DC-
braking the broken wire / offset failure will be shown during operation. In 
this case the terminals must be linked because if storing the failure would 
not allow activation of the safety contacts at standstill.

 

Attention

The terminals X1-X2-X3 have electrical connections to the measuring 
inputs L1-L2-L3. Volt free contacts must be used for bridging. If termi-
nal X3 should be controlled by a PLC via an interface relay this must 
have the necessary insulation between the motor voltage (measuring 
input) and PLC potential.

Summary of Contents for SAFEMASTER S LH 5946

Page 1: ...t Bei Nichtbeachtung kann es zu Personenund Sachsch den kommen Bestimmungsgem e Verwendung Praxishinweise DerStillstandsw chterLH5946istgeeignetzurErkennungdesStillstandes von allen Elektromotoren die...

Page 2: ...es Ger tes A3 A4 Versorgungsspannung f r Halbleiterausg nge ON Halbleiter Meldeausgang f r Schaltzustand der Sicherheitskontakte ERR Halbleiter Meldeausgang f r Fehlermeldung Zur Beachtung Die Ausg ng...

Page 3: ...von Fehlern die die funktionale Sicherheit des Ger tes beeintr chtigen k nnten Die berpr fung auf solche Fehler erfolgt sowohl beim Einschalten der Hilfsspannung als auch zyklisch w hrend des Betrieb...

Page 4: ...Messeingangsleitungen L1 L2 L3 direkt an die Wicklungen des auf Stillstand zu berwachenden Motors angeschlossen werden also z B nicht ber Transformatoren damit eine st ndige berwachung der Wicklungen...

Page 5: ...allm hlich gegen Null heruntergefahren kann eine Entmagnetisierung des Motors stattfinden Es ist dann zu pr fen ob die verbleibende Remanenzspannung ausreicht um eine korrekte Stillstandserkennung zu...

Page 6: ...ngsgrad IEC 60 664 1 Kontakte 11 12 23 24 33 34 43 44 zum Rest 6 kV 2 Kontakte 11 12 23 24 33 34 43 44 zueinander 4 kV 2 Meldekontakte 53 54 zum Rest 4 kV 2 Halbleiter Ausg nge A3 ON ERR A4 zu Rest 6...

Page 7: ...en Sollte bei Wiederanlauf des Motors der Gleichzeitigkeitsfehler bestehen bleiben so ist die Verdrahtung zum Motor auf Fehlerfreiheit gem Anschlussbeispielen zu berpr fen wenn beispielsweise eine der...

Page 8: ...e may lead to personal injuries and damages to property Designated use Practical notes The Standstill monitor LH 5946 is suitable to monitor the standstill of all electric motors that generate a reman...

Page 9: ...A3 A4 Supply for semiconductor outputs ON Semiconductor output indicates state of safety contacts ERR Semiconductor output indicates failures Attention Theoutputs53 54 ONandERRareonlymonitoringoutputs...

Page 10: ...to to detect failures that could influence the safety function of the module The failure check is carried out on power up of the unit and in cycles during normal operation If a failure occurs the out...

Page 11: ...order to provide a correct broken wire detection for the connection wires and motor windings The motor windings must not be disconnected from the measuring wires by motor contactors because broken wi...

Page 12: ...is necessary to check if the remaining remanence voltage is sufficient to guarantee a correct and safe standstill monitoring At high frequencies an increasing damping of the measuring inputs has to be...

Page 13: ...s 11 12 23 24 33 34 43 44 against all others 6 kV 2 Contacts 11 12 23 24 33 34 43 44 against each others 4 kV 2 Indicator contact 53 54 against all others 4 kV 2 Semiconductor outputs A3 ON ERR A4 aga...

Page 14: ...tching the auxiliary supply off and on The reset also takes place when both input signals rise above Uan e g when starting the motor If the simultaneity failure remains active after start of the motor...

Page 15: ...uctions on ne conna t aucun risque r siduel Dans le cas contraire on encourt des riques de dommages cor porels et mat riels Usage appropri Remarques pratiques Le relais de d tection de vitesse nulle p...

Page 16: ...sorties semi conducteurs ON Sortie s c de signalisation de l tat de commutation des contacts de s curit ERR Sortie semi conducteur pour signalisation de d faut Nota Les sorties 53 54 de m me que ON e...

Page 17: ...de d fauts susceptibles de menacer la s curit fonctionnelle de l appareil Le rep rage de ces d fauts a lieu aussi bien l enclenchement de la tension auxiliaire que cycliquement pendant le process L ap...

Page 18: ...afin de garantir un contr le constant de la rupture de conducteur dans les enroulements et dans les c bles Les enroulements du moteur ne doivent pas tre s par s des c bles d entr e de mesure par des...

Page 19: ...mesure L1 L2 L3 du LH 5946 soient toujours reli s par les enroulements du moteur sinon la signalisation de d faut rupture de conducteur emp cherait la lib ration des contacts de sortie En cas de racco...

Page 20: ...de contamination IEC 60 664 1 Contacts 11 12 23 24 33 34 43 44 au reste 6 kV 2 Contacts 11 12 23 24 33 34 43 44 l une et l autre 4 kV 2 Contacts de signalisation 53 54 au reste 4 kV 2 Sorties semi con...

Page 21: ...d enclenchement de la tension auxiliaire Ce d faut dispara t Diagnostics des d fauts aussi automatiquement au red marrage du moteur quand les deux entr es de mesure L2 et L3 re oivent simultan ment d...

Page 22: ...3 43 11 A3 A4 A1 24 34 44 12 ON ERR A2 K4 K5 motor contactor 53 54 DE typische Schaltungskombination mit Not Aus geeignet bis SIL3 Performance Level e Kat 4 EN Typical connection combination with E St...

Page 23: ...ff on M9969_a fuse d star delta timer N mains contactor star contactor triangle contactor With 3 phase connection of LH5946 the star contactor has to be closed after the motor is switched off to detec...

Page 24: ...M10249 A A 8 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 2 x 0 5 1 5 mm2 2 x AWG 20 to 16 A 8 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 2 x 0 5 1 mm2 2 x AWG 20 to 18 A 10 12 mm 1 x 0 5 1 5 mm2 1 x AWG 20 to 16 A...

Page 25: ...N Mounting disassembly of the PS PC terminal blocks FR D montage des borniers ammovibles DE Ma bild Ma e in mm EN Dimensions dimensions in mm FR Dimensions dimensions en mm A B LH 5946 90 45 LH 5946 P...

Page 26: ...es nfo DE Die angef hrten Kenndaten gelten f r die Standardtype Sicherheitstechnische Kenndaten f r andere Ger teausf hrungen erhalten Sie auf Anfrage Die sicherheitstechnischen Kenndaten der komplett...

Page 27: ...27 LH 5946 130910 363 DE Notizen EN Notice FR Note...

Page 28: ...28 LH 5946 130910 363 E DOLD S HNE KG D 78120 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Reviews: