WRM-10P S2 USER’S MANUAL REV 1.0
20
j.
The WRM determines when the resistance reading is stable and displays the resistance
value on the LCD screen as shown below:
The WRM will continue the test and update the resistance values on the LCD screen.
While the test is in progress, you can press the
[ENTER]
key to save the current
readings from the LCD screen to the WRM’s internal working memory. This process can
be repeated as needed for a maximum of 48 times per test.
NOTE
Although this process can be used to store multiple readings when testing a
Load Tap Changer (LTC) or Voltage Regulator, a more convenient method is
also available. Please see section 3.7 for information about performing an
LTC or Voltage Regulator test.
If the
[ENTER]
key is pressed, the data is saved and the following screen will be
displayed on the LCD screen:
Once the test is saved, the WRM will continue testing and display the resistance value
once it has stabilized. You can save the new test results by pressing the
[ENTER]
key.
Press the
[STOP]
key to stop running the test. The test results will be displayed as
shown:
Press any key to continue.
TEST RESULTS
I = 9.987 Amps
R1 = 1.001 m
Ω
TEST IN PROGRESS 12
==> TEST 1 SAVED <==
I = 9.975 Amps
R1 = 1.001 m
Ω Δ
=0%
TEST IN PROGRESS 06
I = 9.972 Amps
R1 = 1.000 m
Ω