Terminals 8 through 12 connect grounded zones 1 through 3. These zones have a
grounded side and cannot be used for fire-initiating devices. Zones 2 and 3 can
also be used for access control with zone 2 providing a bypass feature and zone 3
providing request to exit functionality.
Terminals 13 and 14 connect to zone 4. Zone 4 provides a non-powered Class B
ungrounded zone suitable for connection to fire devices such as heat detectors or pull
stations.
Note:
You must provide a mechanical means of resetting four-wire smoke
detectors or other latching devices on zone 4. The panel does not drop power to
the keypad bus or AX-Bus when a Sensor Reset is performed.
Use the supplied 311 1K Ohm end-of-line (EOL) resistors on each zone. Refer to the
panel programming guide for programming instructions. See the table below and
Figure 7 for more information on wiring the zone terminals.
5
WIRE THE ZONE TERMINALS
ZONE #
RECOMMENDED DEVICE
RESIDENTIAL FIRE DEVICES?
1
Any burglary device
No
2
Door Contact
No
3
REX (PIR or Button)
No
4
Any device
Yes
Table 1: 734N-WIFI Zone Uses