Digital Monitoring Products, Inc. | 734N Series Installation and Programming Guide
33
Zone 2 Bypass Time
Enter the number of seconds to elapse before the bypass
timer expires. The range is 20 to 250 seconds. Press any
select key or area to enter the number of seconds. The
default is
40
seconds. Figure 12 shows how the bypass option
works.
Relock on Zone 2 Change
Selecting
YES
turns the relay off when zone 2 changes state.
Selecting
NO
leaves the relay on when zone 2 changes
state. Turning off the relay allows a long strike time to be
automatically ended upon zone 2 change and relocks the
door. The default is
NO
.
ZONE 2 BYPASS
TIME:
40
5-Second
Strike
40-Second Zone 2
Bypass Entry/Exit Timer
10 seconds before
the bypass time expires,
the device beeps if
the door is still open.
End of
Timer
40
Seconds
A zone open/short is
indicated if the door
remains open.
Figure 12: Zone 2 Bypass Timeline
RELOCK ON ZONE 2
CHANGE?
NO
YES