20
734N Series Installation and Programming Guide | Digital Monitoring Products, Inc.
Set the 734N Address
Keypad Bus Addresses Explained
DMP XR550 Series panels use Keypad Bus addresses 1 through 16. XR150 Series
panels can only use Keypad Bus addresses 1 through 8. Each Keypad Bus address
can accommodate 1 door output and 4 expansion zones. A module with an address
of 2 on the Keypad Bus would represent Door 2 and zones 21‑24. A module with a
keypad address of 14 would represent Door 14 and zones 141‑144.
AX‑Bus Addresses Explained (XR550 only)
DMP XR550 panels are capable of access control expansion using any of the five
AX/LX‑Bus headers (AX/LX500, 600, 700, 800, and 900). An AX‑Bus address
can accommodate 1 door output and 1 expansion zone. Because the 734N Series
module has a built‑in 4‑zone expander, 3 extra zones must be mapped to the
734N. A module with an address of 501 on AX500 would represent Door 501 and
zones 501‑504. A module with an address of 505 on AX500 would represent
Door 505 and zones 505‑508. A module with an address of 701 on AX700 would
represent Door 701 and zones 701‑704.
Note:
Hardwired zone expanders and addressable points and modules do not
communicate on an AX‑Bus. AX‑Bus doors do not have programmable device or
communication types and do not have assignable display areas.