12
734N Series Installation and Programming Guide | Digital Monitoring Products, Inc.
Connect a Wiegand Card Reader
The 734N Series module provides direct 12/24 VDC, 200 mA output to the
reader on the Red terminal connection. Figure 10 shows a reader with wire
colors RED, WHT, GRN, and BLK connecting to Terminals 1, 2, 3, and 4.
The green wire carries Data Zero (D0), and the white wire carries Data One (D1).
The red wire connects 12/24 VDC, 200 mA maximum power and the black wire
is ground.
The wire colors may be different depending on the reader being installed. Refer
to the literature provided with the reader for wire coding, wire distance, cable
type (such as shielded), and other specifications.
Wiegand Status Indicator Outputs
Terminals 5, 6, and 7 provide connections for Remote LED Control, Remote
Annunciation, and Armed Status indicators.
6a