6.3.7 SET-Menu
The SET-Menu allows you to change the operating mode and the size of the used
cartridge of the FlexxPump 125. You can switch between
Hour-Mode -h-
,
Emp-
ty-Time-Mode Et
and
Pulse-Control-Mode
. The Hour-Mode -h- allows you to set the
number of cycles (c) after a pause time (h) in hours. The Empty-Time-Mode Et allows
you to set the emptying time (Et) of the cartridge in months. The Pulse-Control-Mo-
de PUL enables command and control by the controller (PLC) after integration into a
control system (PLC) or similar. Cycles (c) and pause time (h) or emptying time (Et) can
be adjusted after selecting the operating mode in the PRO menu, see Chapter 6.3.9,
6.3.10 or 6.3.11. The cartridge size can be set between 125ml and 250ml.
-h-
Operating mode Hour-Mode
Et
Operating mode Emtpy-Time-Mode
PUL
Operating mode Pulse-Control-Mode
125/250 Changeable parameter of the cartridge size
FlexxPump 125 is switched off (OFF).
Remove the activation and programming key from the bottom of FlexxPump 125 and
place it on the action area.
Hold the activation and programming key on the action surface. The yellow LED lights
up. Leave the activation and programming key on the action area until SET is displayed
in the LCD.
Remove the activation and programming key from the action area.
Ü
The yellow LED disappears; the LCD flashes together with the green LED twice. The
LCD displays the currently set operating mode. You now have the option of changing
the operating mode.