81
ECL-PTU-207 Preloaded Applications
CLG T - Cooling Valve Type
Parameter
Default
Valid
Choices
Description
CLG TYPE
(EC7)
0
UNUSED
Cooling valve is not used
X
1
0-10V
0-10V cooling valve only is used
2
THERMAL
Thermal and 0-10V cooling valve are used
3
ON_OFF
On/Off and 0-10V cooling valve are used
4
FLOATING
Floating and 0-10V cooling valve are used
Table 17: Cooling Valve Type
CLG N - Cooling Valve Polarity
Select Normally Open or Normally Closed depending on your system.
HTG T - Heating Valve Type
Parameter
Default
Valid
Choices
Description
HTG TYPE
(EC8)
0
UNUSED
Heating valve is not used
X
1
0-10V
0-10V heating valve only is used
2
THERMAL
Thermal and 0-10V heat valve are used
3
ON_OFF
On/Off and 0-10V heat valve are used
4
FLOATING
Floating and 0-10V heat valve is used
Table 18: Heating Valve Type
HTG N - Heating Valve Polarity