63
ECL-PTU-207 Preloaded Applications
Room Sensors
Allure EC-Smart-Vue and Allure EC-Smart-Comfort or EC-Smart-Air configuration parameters are
found in the Room Sensors subsection of the Hardware Configuration tab.
Figure 35: Room Sensor subsection
Parameter
Description
EC-Smart-Vue CO
2
Display enable
Select whether the EC-Smart-Vue CO
2
Display is Enabled or Disabled.
EC-Smart-Vue Display
Select what will be displayed on the home screen of the EC-Smart-Vue:
SpaceTemp: Displays the space temperature.
SpOffset: Displays the setpoint offset.
MidSetpoint: Displays the middle setpoint.
EffectSp: Displays the effective setpoint.
EC-Smart-Vue Permissions
Defines how much access a user of the Allure EC-Smart-Vue has to the controller’s
configuration parameters. The Allure EC-Smart-Vue access ranges from full access
to limited access or no access at all. Limited access allows setpoint adjustment only
or setpoint adjustment and airflow balancing.
Regardless of the access level of the Allure EC-Smart-Vue, the controller’s
configuration parameters cannot be modified through the Allure EC-Smart-Vue
except after a password is entered.
EC-Smart-Vue Units
Displays the units being used for the EC-Smart-Vue.
Elevation
For accurate CO
2
concentration levels, input geographic elevation here if elevation is
greater than 500ft (152m) above sea level. By default, the sensor is factory calibrated
to sea level.
EC-Smart-Comfort/Air Sensor Sleep
Time
Enter the amount of time before the sensor goes into standby mode.
EC-Multi-Sensor Zone
Set the designated zone of the multi-sensor to match the remote.
Zone 0 (zero) indicates that the sensor is zone free and can be accessed by any
remote with any zone designation if it is within range.
Configuring the Preloaded Applications