ECL-PTU-207 Preloaded Applications
Network Variables Output
nvoSpaceTemp
This output network variable is used to monitor the effective space temperature that the Space Com-
fort Controller is using for control.
If the input nviSpaceTempAvg has a valid value, this output will be equal to the average of all values
received by nviSpaceTempAvg.
If the input nviSpaceTemp has a valid value and nviSpaceTempAvg is not valid, this output will echo
the value of the input.
If a valid value for nviSpaceTemp does not exist, the locally wired sensor value is used.
If neither value is available, the output will send the invalid value.
The locally wired sensor priority order is the following:
£
SI3 Space Temperature
£
EC-Smart-Vue temperature
£
EC-Smart-Comfort temperature
£
EC-Remote Space Temperature
£
SI3 Return Temperature
£
EC-Multi-Sensor Temperature
ID
Units
Valid Range
Default Value
nvoSpaceTemp
SNVT_temp_p
N/A
N/A
nvoUnitStatus
This output network variable is available to report the Space Comfort Controller status.
It combines the operating mode, the capacity of heating and cooling used and an indication if any
alarms are present in the object. SNVT_hvac_status allows this information to be provided in one net-
work variable.
Refer to Effective Heat/Cool Output novHeatCool for additional information regarding the value re-
ported in the mode field.
The outputs are linked to the following fields:
Field
Description
mode
nvoHeatCool
heat_output_primary
heating valve control
heat_output_secondary
electric heater control
cool_output
cooling or change-over valve control
econ_ouput
Damper control
fan_output
Fan control
inAlarm
This input manage 7 digital alarms :
(1) : SpaceTempFault
(2) : Light Extension 1 offline
(4) : Light Extension 2 offline
(8) : Blind Extension 1 offline
(16) : Blind extension 2 offline
(32) : MultiSensor offline
(64) : EC-Smart-vue offline
(128) : additional digital alarm in gfx.
ID
Units
Valid Range
Default Value
nvoUnitStatus
SNVT_hvac_status
N/A
N/A
Variables