39
ECL-PTU-207 Preloaded Applications
SensorSleepTime (ConstantNum8)
This variable is used to configure the sensor sleep time of the EC-Smart-Comfort sensor. If set to 0,
the sensor sleep time is disabled
ID
Units
Valid Range
Default Value
Constant Numeric 8
seconds
N/A
0 second
SlaveTempDelta (ConstantNum14)
This variable is used to configure the minimum temperature variation before updating the nvoSlave-
Info.SpaceTemp value.
ID
Units
Valid Range
Default Value
Constant Numeric 14
Degrees-celsius (°C)
N/A
0,1 °C
SlaveDelayMotion (ConstantNum15)
This variable is used to configure the motion stop delay before updating the nvoSlaveInfo.Motion value
ID
Units
Valid Range
Default Value
Constant Numeric 15
seconds
N/A
10 seconds
ChangeOverCoolOn (ConstantNum16)
This variable is used to configure the water temperature below which 2 pipes change-over systems
are considered to be in cooling mode.
ID
Units
Valid Range
Default Value
Constant Numeric 16
Degrees-celsius (°C)
N/A
16 °C
ChangeOverCoolOff (ConstantNum17)
This variable is used to configure the water temperature above which 2 pipes change-over systems
are considered to be in heating mode.
ID
Units
Valid Range
Default Value
Constant Numeric 17
Degrees-Celsius (°C)
N/A
20 °C
Variables