Steps to configure test mode.
The test mode configuration of a zone is activated by
pressing the key of the zone that you want to configure in that mode. To deactivate the
test mode for a zone, follow these steps after enabling access to the keypad (section 6.3,
point G):
•
PRESS THE KEY OF THE CORRESPONDING ZONE: Test mode is activated.
•
PRESS THE GENERAL TEST KEY: Test mode is deactivated.
6.4.6. Out of service mode
The unit enters out of service mode when there is no power supply and the voltage of the
batteries is below 22 V. When in this mode, the control panel will not display any event
that occurs in the system and, therefore, no alarms or faults will be detected.
The fact that the unit is out of service is indicated as follows:
•
GENERAL FAULT INDICATOR STEADILY LIT
•
OUT OF SERVICE INDICATOR LIT STEADILY
•
AUDIBLE INDICATOR ACTIVATED CONTINUOUSLY
•
FAULT OUTPUT ACTIVATED
Actions in out of service mode.
The only actions that can be taken are as follows:
•
PRESS THE MUTE BUZZER KEY TO STOP THE AUDIBLE INDICATOR.
•
RESTORE THE MAINS SUPPLY (220 V).
•
REPLACE THE BATTERIES WITH ONES THAT ARE CHARGED.
6.4.7. System fault mode
System fault mode occurs when a critical situation has occurred in the system and it is
not working correctly. System faults are indicated as follows:
•
GENERAL FAULT INDICATOR STEADILY LIT
•
OUT OF SERVICE INDICATOR LIT STEADILY
•
AUDIBLE INDICATOR ACTIVATED CONTINUOUSLY
•
FAULT OUTPUT ACTIVATED