If using non-polarised sounders or bells, it is
necessary to install a 1N4007 diode to avoid the
effect of the reverse current.
4.2.1. Sounder timer
On the bottom left part of the
MAIN BOARD
there is
a double line with pins to configure the time delay
of the sounders. This time delay is configured by
placing the jumper in the corresponding position
of the desired timer (between 0 and 10 minutes).
4.3. Wiring of 24 VDC auxiliary output
CCD-020/040 control panels have 1 24 VDC
auxiliary output that is used to supply power to
the devices that require this power. Its maximum
current is 450 mA and it is protected by a fuse. Do
not use this output to supply power to devices with
excessive power consumption when on standby.
This output is not resettable.
4.4. Wiring of voltage-free relay output
CCD-020/040 control panels have a fault
relay and an alarm relay. These relays, with a
maximum current of 2 A, switch when the control
panel detects an alarm or fault. The fault relay is
energised and, if there is a loss of power, it will
signal the respective fault.
NO
TE:
If using the contacts to
supply power to inductive loads, use
a protection diode to avoid damaging
the contacts.
+ -
+ - + - + - + -
c nc na c nc na
+ - + -
4K7 resistor
4K7 resistor
3 4
4K7 resistor
+ -
+ -
z1
+ -
z2
+ -
z3
+ -
z4
c nc na
alarm
c nc na
fault
snd1
+ -
snd2
+ -
24v aux
4K7 resistor
1 2
1 2
3 4
1 2 3 4
+ -
snd1
SW 10MIN
9MIN 8MIN 7MIN 6MIN 5MIN 4MIN 3MIN 2MIN 1MIN 0MIN
DELAY SND
+ -
24 V aux
+ -
+ - + - + - + -
c nc na c nc na
+ - + -
ResistencIa 4K7
ResistencIa 4K7
3 4
ResistencIa 4K7
+ -
+ -
z1
+ -
z2
+ -
z3
+ -
z4
c nc na
alarm
c nc na
fault
snd1
+ -
snd2
+ -
24v aux
ResistencIa 4K7
1 2
1 2 3 4
1 2 3 4
c nc no
ALARM
c nc no
FAULT