23
EN
4.5. Power supply wiring
4.5.1. Battery wiring
Convention control panels require two
12 VDC batteries connected in series.
The capacity of these batteries must be
2.3 A/h.
The wire jumper supplied with the control
panel must be connected so that the
+ pole of one battery is connected to the
- pole of the other.
The batteries are placed in a vertical
position on the left side of the case, as
shown in the image to the right.
4.5.2. Wiring to the mains
The control panel must be connected to
the mains using an external double pole
circuit breaker and a cable with a 1.5 mm²
cross section. The mains voltage must be
230 VAC.
⚠
W
ARNING!: Do not
connect the control panel
to the mains if you have
not finished wiring the
system's components. Al-
ways disconnect the circuit
breaker before handling
the connections to avoid
any risk of electrocution.
2
1
3
4
⏚